Hoyles Redimon v3 Monitor User Manual

Dimensions, Redimon, A b c d

Advertising
background image

Dwg No: 60136 Oct 2011

Redimon is a latching monitor unit which fully monitors two
lengths of

to give independent alarm and fault

conditions. An End of Line resistor is fitted at the remote end of
each length of

. Pressing the

creates a

short circuit which will be detected as an alarm condition. If the

becomes disconnected in any way a fault condition

is generated. The Redimon requires 12 volts dc and provides
volt free changeover contacts for both alarm and fault. A Reset
button is provided.

Panic Strip

Panic Strip

Panic Strip

Panic Strip

Redimon can also be used to create a double pole EOL circuit

for any

momentary action normally open device. E.g. Push button.

Redimon is supplied with two 6k8 end of line resistors fitted
to the terminals AB and CD for test purposes. If only one
length of

is being monitored one of these

resistors should be left in either AB or CD terminals and the
other terminals used for the

.

Panic Strip

Panic Strip

Any other type of non-latching open circuit button or switch
could be wired across Panic Strip circuits to complement
the system as in Panic Strip 2 shown below.

Under normal circumstances the GREEN LED will be illuminated to show that power is on and the circuits are healthy. When
either

is operated the RED LED will illuminate and the alarm relay will change over. If either of the

circuits becomes disconnected the RED and GREEN LEDs will alternate and the fault relay will operate, this will restore
when the circuit has been repaired. To reset the

from an alarm condition press the Reset button.

Panic Strip

Panic Strip

Panic Strip

Dimensions in mm

Dimensions

12 Volts dc power
45ma max

Alarm output
Fault output

Panic Strip Type 3

Panic Strip Type 3

E.O.L 6k8

E.O.L 6k8

v3

Redimon

Latching monitor unit for Panic Strip

Use these changeover contacts to connect to the personal attack circuit of your intruder alarm.

Use these changeover contacts to connect to the tamper circuit of your alarm

11 - 14 volts dc at all times. Quiescent current 30ma Max current 45ma

ALARM

OUTPUT

NO

NO

COM

RELAY 1

RELAY 2

COM

NC

NC

FAULT

OUTPUT

T1

T2

TAMPER

SWITCH

6K8 Terminating resistors

Panic Strip

Type 2

Panic Strip

Type 3

Panic Strip

Type 3

Panic Strip

Type 2

These contacts are rated @ 30vdc 1A

Optional open circuit
non-latching push button

A B C D

NOTE

Panic Strip

SHOULD NEVER BE

CONNECTED DIRECTLY TO MAINS
VOLTAGE CIRCUITS.
IT IS ONLY RATED FOR SAFE WORKING
ON 43 VOLTS MAXIMUM.

T1 and T2 are normally closed. Opening this circuit will cause a fault
until the circuit is closed again. If wired as shown, removing the unit
cover will cause a fault to be indicated, until the cover is replaced.

T. 01744 886600 F. 01744 886607 E. [email protected] W. www.hoyles.com