12

parameters specific to the job site.

The SRCM can take as input, the signal from two separate pressure transducers as well

as temperature, humidity, and user defined (ex. CO

2

) inputs for up to two rooms. These

are configured for either Primary Room or Secondary Room (an anteroom is an example

of a secondary room). When two transducers are used, the Home screen display of the

SRCM can toggle between each space to indicate the status of each room momentarily,

cycling from one to the other a few seconds apart

or the display can be locked on either

of the two rooms.

*If Ch1 is selected for the Primary room, it will not be an available option for the Sec-

ondary room.

Use the radio button to select the setup parameters for either the Primary Room or Sec-

ondary Room.

Change, if necessary, to match sensor being used. OnBoard is the default, which uses

the sensor manufactured on-board the unit. Alternatively, an external sensor (also

known as “external transducer” such as a Setra 264 or Setra 267) may be used. If an

external sensor is used, change this selection to ADC Ch1 (Analog Input 1) or ADC

Ch-2 (Analog Input 2). The FS output and range of the external sensor will need to

be entered. If the OnBoard Sensor is selected, a box is shown displaying the pressure

range and engineering unit.

Change, if necessary, to match sensor being used, if there is one present. None is the

default. An external sensor (also known as “external transducer” such as a Setra 264

or Setra 267) may be used for the secondary room, or anteroom. If an external sensor

is used, change this selection to ADC Ch1 or ADC Ch2, which use Analog Input 1 or

Analog Input 2, respectively. The FS output and range of the external sensor will need

to be entered.

Setup Unit

Primary Room sensor:

• OnBoard Sensor

• External Ch1

Secondary Room sensor:

• External Ch1*

• External Ch2

Setup selection to

configure either

Primary or

Secondary Room

Primary room pressure signal

output (AO) scale and units:

• 4-20 mA

• 0-5 Vdc

• 0-10 Vdc

Room label of selected room,

either Primary or Secondary

depending on ROOM radio button

Full Scale (FS) range of transducer

selected, Primary or Secondary

Pressure units, either “ WC or Pa

ROOM - Primary

or Secondary

Primary Room

Sensor

Secondary Room

Sensor