displayed on the Operating Condition section of the Home screen. The display

contrast level is adjusted using Adjust Contrast Level, with selections from

1-4. After modifying this parameter, press Save & Exit to view the brightness

and contrast on the Home screen display. Depending on the lighting and view-

ing conditions in the final space, different contrast levels can improve read-

ability of the SRCM.

This function is used to improve the stability of the pressure value displayed

on the Home screen, so significant digits do not change rapidly. It is used

more often in environments where the user requires higher display resolution

(4 digits) but the ambient pressure is unstable. By increasing the number, the

effective number of measured data points is increased and a weighted aver-

age is developed. Input the number in tenths of a second for the response time

of the display to a pressure change. There is no ratcheting of the display or

a deadband. The pressure change is very smooth. For example, entering 10

equates to the display reaching final value in 1 second. Entering 2 equates to

final value in 2 seconds.

Display Averaging does not affect the Analog Output response time, only the

apparent stability of the pressure display. Display Averaging also does not af-

fect Alarm Thresholds or Alarm Delay.

This function defines what pressure value is shown on the Home screen under

normal operating conditions. This can be Primary Only, Secondary Only, or

Toggle, depending on what room is most important for visual pressure verifi-

cation.

If this is set to Primary Only, then the Home screen will show the pressure

value read by the primary pressure transducer (either on-board, or the alter-

nate primary transducer configured from a separate transducer, if one is used).

If a secondary transducer is in use, and an alarm condition occurs in the sec-

ondary room, the display will toggle and remain on the secondary room and

pressure value as long as the alarm condition is present in that space.

Advanced Tab–
Customizing the Operation
Condition Screen

When finished making changes, press Save & Exit to store

the modifications. Or press Exit to discard changes and return

to the previous screen

Primary Pressure Resolution

The number of significant digits

displayed for the pressure value

(1-4)

Contrast level of Home

screen. Adjust from 1-4 for

readability in varying

lighting conditions

Define Supervisor and Operator

passwords. Enable or Disable use of

passwords

Display Averaging.

Select a value from 1-40

What Pressure To Display:

• Primary Only

• Secondary Only

• Toggle

Configure if you want to enable

banner

Display Averaging
(tenths of seconds)

What Pressure To
Display