If this is set to Secondary Only, then the Home screen will show the pres-

sure value read by the secondary pressure transducer (anteroom for ex-

ample). In this case, if an alarm condition occurs in the primary room, the

display will toggle and remain on the primary room and pressure value as

long as the alarm condition is present in that space. If no Secondary Room

is configured on the Setup Unit screen, attempts to choose Secondary Only

will result in the error “Secondary room source is NONE.”

If this is set to Toggle, then the Home screen will show the pressure value

for both rooms, alternating back and forth momentarily (approximately 10

seconds apart). If an alarm condition occurs in either room, the display will

toggle to the appropriate room and pressure value and remain on that room

as long as the alarm condition is present. If both rooms are in alarm, then

the alarm condition and pressure values will toggle.

This setting shows the number of digits after the decimal point

for the default screen pressure displays. This setting affects the

primary and secondary room settings.

The password function provides security against changed configurations by

unauthorized users. This is accomplished by using two levels of password

protection. These can be enabled or disabled.

The Operator level allows access to change between Active and Standby

room modes, but no other changes.

The Operator is the person that has day-to-day interaction with the monitor

to change operating modes from Active` mode to Standby (where no alarms

are active), the operator can also respond to local audible and visual alarms.

This can be a Nurse or a Lab Technician. The SRCM was designed to make

interaction with the unit as easy as possible for the Operator. Changes to

messages and to the room mode requires simply touching active areas of

the display. If Operator Password is enabled then a password will be need-

ed before the change can be made.

The Supervisor Level allows full access to all menus. The Supervisor has

access to all levels of the menu structure. This mode is used during initial

configuration and follow-on reconfiguration.

NOTE: The master Supervisor password is 351, and will work for any

condition where a user may need to reset passwords.

Pressure Resolution

Supervisor and

Operator Passwords