Setup alarm, Set time & date screen – Setra System SRCM User Manual

Page 22

Advertising
background image

22

Define which room the Setup Alarm

conditions will apply to

For each room (Primary or Sec-

ondary), define whether the room

pressure will be Positive, Neutral,

or Negative

Setup Alarm

The Setup Alarm screen permits authorized users (based on password level) to con-

figure alarm behavior, such as the duration of alarms, methods of clearing alarm

condition, and how alarms are acknowledged. It also sets the room mode to positive,

negative or neutral room.

Latch Alarm

If enabled, causes the display of red ALARM on the Home screen

to remain, even if room pressurization returns to NORMAL. Latch

Alarm enabled requires that an alarm event be acknowledged and that

the pressure returns to within the normal range. This is useful because

it forces recognition that an alarm event occurred. The alarm will still

be on even if the pressure returns to normal range. Only when the

alarm is acknowledged will alarming cease. When disabled, the alarm

will be silenced when the pressure returns to normal range without

requiring acknowledgement.

When a Latch Alarm occurs, the Home screen displays a RESET

button to the right of the Menu button. Press the RESET button to

acknowledge and reset the Latch Alarm condition.

Alarm Delay

Time between when the pressure went outside alarm setpoints and

when the unit goes into alarm mode. This is useful in preventing false

alarms. For example, if Alarm Delay is set to 20 seconds, the staff has

20 seconds to open a door, enter the room and close the door before

the alarm sounds (if audible alarms are enabled). Alarm Delay also

applies to alarms annunciated to a remote annunciator via the SRCM

Digital Output (hardware configuration).

Set Time &
Date Screen

The Set Time & Date tab is used for setting the time and date of the SRCM. This time

and date is used to time stamp the event log. See Event Log Section.

Note: If power is lost to the unit, the time, and date need to be reset. If BACnet is used and is connected

to the network, the time and date will automatically be retrieved.

The date format is DD-MM-YYYY.