Audible Alarm

Enables or disables the audible buzzer. Regardless of whether audible

alarming is enabled or disabled, the red ALARM condition will show

on the Home screen, annunciate to an SRAN, and propagate to a

configured Digital Output. If an alarm occurs and the audible alarm is

enabled, a new SILENCE button will appear on the Home screen so

that the operator can silence the audible alarm. The audible alarm is

silenced only for the period of time defined by Mute Time Out.

Mute Time Out

Sets the time (in seconds) that the alarm will remain silent after press-

ing the SILENCE button before the audible alarm resumes again.

This assumes that the room pressure condition is still outside the

normal setpoint operating limits. Mute Time Out can be set from 0 to

9998 seconds. Entering a value of 9999 will silence the audible alarm

“forever,” as long as a new alarm condition does not occur.

Digital Input (DI)

Used for monitoring the door status, open or closed. The DI is a Nor-

mally-Closed dry contact. A door jamb or valve pressure switch must

be wired to the terminals labeled DOOR in the rear of the unit. When

the door opens the contact will open, and this will show a yellow

DOOR Warning on the Home screen.

The Door Alarm will suppress

alarms if they are generated at the same time that the door is open.

Deadband

is adjustable from 0 to 10% and represents the region within the

setpoint range where yellow WARNING is displayed on the Home

screen to indicate that the pressure is near ALARM limits. If set to

0, no WARNING will occur, only ALARM when the pressure value

reaches setpoints. If set to any other value, WARNING will be dis-

played if the pressure value reaches that percentage of total pressure

setpoint range.

When the unit goes outside of the deadband range the alarm will oc-

cur. The alarm will remain until the pressure returns within the alarm

limit range (or acknowledged Latch alarm) minus the setpoint.

Buzzer Volume

The buzzer volume can be adjusted from one—four, with four being

the highest sound level. The alarm buzzer is disabled using audible

Audible Alarm disable function.