Setra System SRCM User Manual

Page 25

Advertising
background image

25

For each space, Primary Room or Secondary Room, this screen is used to define the alarm

setpoints. When the room is then set to Positive, Neutral, or Negative, the setpoints and con-

ditions configured here are in effect for alarm and warning conditions.

The SRCM has a great deal of flexibility to define alarm conditions. Alarms and warnings

can be configured for primary and secondary rooms, and for the door. Room display can

toggle between Primary and Secondary. The following table outlines what will occur in

terms of priority and display under normal and alarm conditions.

N=Normal; A=Alarm

Toggle

High Priority

Display

Text (Maxi-

mum eight

Background

Remarks

Primary

Pressure

Secondary

Pressure

Disabled

N

N

Normal

Green

Displays primary pressure

or secondary pressure based

on the selection

in the setup

display screen.

Disabled

N

A

Alarm

Red

Shows Alarm for second-

ary room if secondary room

is selected for the display.

If the pressure to display is

selected as Primary, display

switches to the secondary

room to show the alarm.

Disabled

N

A

Alarm

Red

Shows Alarm for second-

ary room if secondary room

is selected for display. If

the pressure to display is

selected as Primary, display

switches to the secondary

room to show the alarm.

Alarm Set Point

Alarm Matrix