Calibration and self-test – Setra System SRCM User Manual

Page 27

Advertising
background image

27

Toggle

High Priority

Display

Text (Maxi-

mum eight

characters)

Background

Remarks

Primary

Pressure

Secondary

Pressure

Disabled

A

N

Alarm

Red

Shows Alarm for second-

ary room if secondary room

is selected for display. If

the pressure to display is

selected as Primary, display

switches to the secondary

room to show the alarm.

Disabled

A

A

Alarm

Red

Display toggles between pri-

mary and secondary room.

Disabled

A

A

Alarm

Red

Display toggles between pri-

mary and secondary room.

Enabled

N

N

Normal

Green

Toggle between primary and

secondary room.

Enabled

N

A

Alarm

Red

Shows secondary alarm.

Display stops toggling.

Enabled

N

A

Alarm

Red

Shows secondary alarm.

Display stops toggling.

Enabled

A

N

Alarm

Red

Shows primary alarm. Dis-

play stops toggling.

Enabled

A

N

Alarm

Red

Shows primary alarm. Dis-

play stops toggling.

Enabled

A

A

Alarm

Red

Display toggles between pri-

mary and secondary room.

Enabled

A

A

Alarm

Red

Display toggles between pri-

mary and secondary room.

This page is used for calibration of the internal pressure transducer sensor

and testing operation of hardware circuitry. Calibration is only required for

highly accurate measurement needs such as those needed to comply with

federally mandated regulations. Calibration should only be performed by

qualified personnel.

1. Select Primary or Secondary room. When selected, the gray box to the

right will indicate if the calibration will be applied to the on-board sensor or

the external sensor (Analog Ch1 or Analog Ch2). The indicated pressure is

shown.

2. Calibration of the on-board sensor requires that the faceplate be removed

and the captive screw holding the display cover must be loosened (at the

bottom-center of the display bracket).

3. Lift the cover to expose the clear and red tubing connecting the on-board

sensor to the pressure fittings in the rear of the unit.

4. Remove the tubing from the high and low ports (red and clear tubing).

This disconnects the sensor from the room pressure.

5. After calibration, replace the red and clear tubing.

Calibration and

Self-Test