4. APDU Timeout - Indicates the amount of time in milliseconds between retrans-

missions of the APDU requiring acknowledgement for which no acknowledge-

ment has been received. The default value for this property will be 3,000 ms and

max can be 65535.

Save and Exit to save settings or cancel to cancel setting changes.

Once this is complete disable the BACnet setup by moving the dip switch position

1 to off (left ) position.

Press Save and Exit.

5. After the unit returns to the main menu screen, disconnect the power to the unit

and reconnect in order to boot up with the proper MAC address and Device In-

stance. The power can also be cycled by removing Jumper JP1 and then reconnect-

ing.

The unit can also be configured through the BACnet interface as well as through

the Touch Screen User Interface.

Five position dip switch

location

Removing the jumper

causes power loss.

Re-insert the jumper to

restore power.