Type d'objet valeur analogique, Guide dʼinstallation / utilisation 99 français – LG PQNFB17B0 User Manual

Page 423

Advertising
background image

Appendice 2

• Type d'objet Valeur analogique

Propriété Identificateur

Propriété Type de donnée

BACnet

BNU-BAC

Object_Identifier BACneObjectIdentifier

R

R

Object_Name CharacterString

R

R

Object_Type BACnetObjectType

R

R

Present_Value Real

R4

W

Description CharacterString

O

R

Status_Flags BACnetStatusFlags

R

R

Event_State BACnetEventState

R

R

Reliability BACnetReliability

O

-

Out_Of_Service Boolean

R

R

Units BACnetEngineeringUnits

R

R

PriorityArray BACnetPriorityArray

O1

-

RelinquishDefault Real

O1

-

COV_Increment Real

O2

-

Time_Delay Unsigned

O3

-

Notification_Class Unsigned

O3

-

High_Limit REAL

O3

-

Low_Limit REAL

O3

-

Deadband REAL

O3

-

Limit_Enable BACnetLimitEnable

O3

-

Event_Enable BACnetEventTransitionBits

O3

-

Acked_Transitions BACnetEventTransitionBits

O3

-

Notify_Type BACnetNotifyType

O3

-

Event_Time_Stamps

BACnetARRAY[3] of BACnetTimeStamp

O3

-

Profile_Name CharacterString

O

-

Guide dʼInstallation / Utilisation 99