Bacnet point list : indoor unit, Installation/owner manual 55 english – LG PQNFB17B0 User Manual

Page 55

Advertising
background image

Objects (BACnet/IP)

BACnet Point List : Indoor Unit

One indoor unit has the following 22 objects.

Point

No.

Name

ObjectName Product Name

(XXX : Unit address)

Object

Type

Unit

Inactive

Active

Text-0

Text-1

Text-2

Text-3

Text-4

Text-5

1

ON/OFF (Setting)

StartStopCommand_XXX

BO

Stop

Start

2

ON/OFF (Status)

StartStopStatus_XXX

BI

Stop

Run

3

Lock (Setting)

LockCommand_XXX

BO

Permit

Prohibit

4

Lock (Status)

LockStatus_XXX

BI

Permit

Prohibit

5

-

-

-

6

-

-

-

7

Mode (Setting)

ModeCommand_XXX

MO

Cool

Dry

Fan

Auto

Heat

8

Mode (Status)

ModeStatus_XXX

MI

Cool

Dry

Fan

Auto

Heat

9

Swing (Setting)

SwingCommand_XXX

BO

Stop

Run

10

Swing (Status)

SwingStatus_XXX

BI

Stop

Run

11

Fan Speed (Setting)

FanSpeedCommand_XXX

MO

Low

Middle

High

Auto

12

Fan Speed (Status)

FanSpeedStatus_XXX

MI

Low

Middle

High

Auto

13

Set Room Temperature

SetRoomTemp_XXX

AV

°C

14

Room Temperature

RoomTemp_XXX

AI

°C

15

Alarm

Alarm_XXX

BI

Normal

Abnormal

16

Error Code

MalfunctionCode_XXX

AI

Reference LG Original Error Code

17

-

-

-

18

-

-

-

Installation/Owner Manual 55

ENGLISH

Advertising