Detailed Explanation of Object

Detailed Explanation of Object

1) Common to All Objects

Objects related to the air conditioner in communication are treated on the BACnet as described
below.

- Air Conditioner in Normal Communication

Other BACnet devices can access each object related to the air conditioner.

- Air Conditioner Unconnected

It seems to other BACnet devices that no objects related to the air conditioner exist.
Therefore, when the ReadProperty/WriteProperty service is received, the following ErrorPDU will
be returned.
Error class: OBJECT; Error type: UNKNOWN_PROPERTY

- Air Conditioner Communication Error

Other BACnet device can access the objects related to the air conditioners, but the
Present_Value Property will be read in a value immediately before the communication error.

2) Run/Stop (Setting)

Point number: 1

Object name: StartStopCommand_XXX (XXX: A/C unit address)

Object type: Binary Output

Meaning: This object is used to give Run/Stop commands to the air conditioner.

Present_Value property:

ACTIVE: Run command

INACTIVE: Stop command

Remarks: 1. The command executed is transmitted to the A/C regardless of the status of the A/C.

2. Present_Value property will not be used if a property has never been set in the past.

3) Run/Stop (Status)

Point number: 2

Object name: StartStopStatus_XXX (XXX: A/C unit address)

Object type: Binary Input

Meaning: This object is used to monitor the Run/Stop status of the air conditioner.

Present_Value property:

ACTIVE: Run

INACTIVE: Stop

Remarks: If there is an operation error, the Present_Value property will be set to ACTIVE

regardless of whether the A/C is in operation or not.

Installation/Owner Manual 75