Report Function

A request for COV registration is accepted through the SubscribeCOV service.

1) Setting of Confirmed or Unconfirmed COV

This item is supported according to the BACnet Specifications.

2) Setting of the desired lifetime of the subscription

This item is supported according to the BACnet Specifications.
When COV notification is made at the time of status change, the difference between the registered
time and present time will be calculated. If the difference is greater than the registered lifetime of
the subscription, the subscription will be judged expired and deleted. Therefore, if a clock time
change is made, the lifetime of the subscription may differ from the value that has been set.

3) Memory after Interruption of Power Supply to System

This item is not supported. Registration information is not stored in the memory, and will be lost
when the power is turned off. According to the BACnet Specifications, It is not required to
guarantee preservation of subscriptions across power failure.

Supported COV service is shown in the follow table

COV(Change of Value) Notification

Service

Object

Product

On/Off (status)

Binary Input object property

Indoor, vent

Lock On/Off (status)

Binary Input object property

Indoor, vent

Mode Lock (status)

Binary Input object property

Indoor

Wind Flow Lock (status)

Binary Input object property

Indoor

Set Upper Temperature (status)

Analog Input object property

Indoor

Set Lower Temperature (status)

Analog Input object property

Indoor

Operation mode (status)

Multistate input object property

Indoor, vent

Swing (status)

Binary Input object property

Indoor

Filter Sign

Binary Input object property

Vent

Fan Speed (status)

Multistate Input object property

Indoor, vent

Set Room Temperature

Analog value object property

Indoor

Room Temperature

Analog input object property

Indoor

Alarm

Binary Input object property

Indoor, vent

Error Code

Analog Input object property

Indoor, vent

User mode

Multistate input object property

vent