value

not used (set in 0% usually)

0 = Fan direction fixed for air conditioner product

state

1 = Fan direction auto for air conditioner product

Default Value

5) Fan direction auto input/output (Only applies to air conditioner)

Valid Range

SNVT_switch

( Index : 95 )

NV

Filed

Operation

Function

Fan direction auto command input

Input

Using NV

Network input variable : SNVT_switch nviSwing_n

Operation

It controls the fan direction of each product (air conditioner/ventilation)

Function

Fan direction auto status display

Output

Using NV

Network output variable : SNVT_switch nvoSwing_n

Operation

It monitors the fan direction of each product (air conditioner/ventilation)

6) Temperature setting input/output (Only applies to air conditioner)

Function

Set temperature range input

Input

Using NV

Network input variable : SNVT_switch nviSetPoint_n

Operation

It controls the temperature setting of each product (air conditioner/ventilation)

Function

Set temperature range status display

Output

Using NV

Network output variable : SNVT_switch nvoSetPoint_n

Operation

It monitors the set temperature of each product (air conditioner/ventilation)

At Cool mode : 18 ~ 30°C