10) Total operation/stop air conditioner indoor unit

Function

Total stop command input

Input

Using NV

Network input variable : SNVT_switch nviTotalONOFF_indoor

Operation

It turns ON or OFF all the indoor units.

11) Total operation/stop ventilation indoor unit

Function

Total stop command input

Input

Using NV

Network input variable : SNVT_switch nviTotalONOFF_indoor

Operation

It turns ON or OFF all the ventilation units.

0 = Not used

value

1 = Quick mode

2 = Power save mode

3 = Heat

9) Ventilation function command (Only applies to ventilation product)

Valid Range

SNVT_count

( Index : 8 )

NV

Filed

Operation

Function

Ventilation user operating mode input

Input

Using NV

Network input variable : SNVT_count nviUser_n

Operation

It controls the product function of each ventilation product.

Function

Ventilation user operating mode status

Output

Using NV

Network output variable : SNVT_count nvoUser_n

Operation

It monitors the function status of each ventilation product.

value

not used

state

1 = All ON indoor/Vent unit

0 = All OFF indoor/Vent unit

Default Value

Valid Range

SNVT_switch

( Index : 95 )

NV

Filed

Operation