GE Box-Timer GE Time Switch 15251 15252 and 15253 User Manual

Time switch, Warning

Advertising
background image

SPECIFICATIONS

Input Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based upon
dipswitch configuration.

15252

NEMA 3R Indoor & Outdoor BM-A301US5-O2

15253, 15251

NEMA 1 Indoor

BM-A301US5-I2

15250

NEMA 3R Indoor & Outdoor EM-A301US9-O2

Switch Rating: DPDT Models

Normally Open Contacts

40A Resistive, 120-277Vac.
30A General Purpose, 120-277Vac.
20A Resistive, 30Vdc
1 HP, 120Vac ; 2HP, 240Vac
20A Ballast, 120-277Vac.
15A Tungsten, 120Vac
800VA, Pilot Duty, 120Vac.
720VA, Pilot Duty, 240Vac.
TV-5, 120Vac

Normally Closed Contacts

30A Resistive, 120-277Vac
15A General Purpose, 120-277Vac
15A Resistive, 30Vdc
20A Ballast, 120-277Vac
1/4HP, 120Vac; 1/2HP, 208-240Vac.
290VA, Pilot, 120Vac.
360VA, Pilot, 208-240Vac.

NOTE: If loads are connected to both NC and NO contacts, both contacts are
derated to 67% of the above values.

ENVIRONMENTAL RATINGS

Ambient Temperature: –40F to 130F
Humidity: 0-95% RH, Non-condensing

WIRING CONNECTIONS

Screw clamp terminals for up to 2 AWG #8 wires
per position. For supply connections, use 8AWG or larger wires suitable for at
least 105° C. Use copper conductors only.

LIGhTS

Power LED (Orange) – Light illuminates when power is applied to
the timer
Status LED (Green) – Light illuminates when power is applied to load.

INSTALLATION

CAUTION: Before wiring or service, power to this time switch and the
equipment it controls must be turned off. Turning off the timer switch only
will not prevent a shock hazard. Replace cover plate within housing before
supplying power to time switch. Installation should be performed by a licensed
electrician only. Before installing this product read all instructions carefully.
Remove protective cover panel within time switch housing by removing
screws located above timer face and at the bottom of the cover panel.

DIPSWITCh CONFIGURATION

WARNING:

Failure to properly configure the dipswitch will result in

damage to the unit and void the warranty! Before installing and wiring the GE
Time Switch, proper configuration must be selected. This is accomplished as
follows:

INPUT VOLTAGE DIP SWITCh SETTING:

1.

Do not apply power to the timer prior to setting correct Input Voltage DIP
switch.

2.

Determine the input voltage which will be applied to the timer (i.e. L1 and
L2/N terminals, see wiring diagrams)

3.

Set the DIP switch according to the diagram below.

NOTE: Unit is shipped with DIP switches set for 277VAC Input Voltage

CAUTION: Do not check circuits by “sparking” wires to terminals. Damage to
the timer may result.

NOTE: For outdoor locations (model GE 15252), rain tight or wet location
conduit hubs that comply with requirements of UL 514B (standard for fittings
for conduit and outlet boxes) must be used.

1.

Remove 2 screws retaining the interior cover panel and remove panel
by prying out with a thin blade at the top.. Select knockouts to be used.
Remove the inner 1/2” knockout by inserting a screwdriver in the slot
and carefully punch knockout loose. Remove slug. If the 3/4” knockout
is required, remove the outer ring with pliers after removing the 1/2”
knockout. Smooth edges with knife if necessary.

2.

Place enclosure in desired mounting location and mark the three
mounting holes.

3.

Drill holes for #10 screws, start screws in holes.

4.

Place enclosure over screws and tighten screws.

5.

Connect conduit hubs to conduit before connecting the hubs to the
enclosure. After inserting hubs into enclosure, carefully tighten hub lock
nut. Do not over-tighten.

Dipswitch Setting continued:
6.

Install in accordance with all applicable National and Local code
requirements. See Figure 1 and wiring diagrams.

7.

Replace interior cover panel and 2 screws.

Time Switch

15251/15253

Indoor

NEMA 1-Rated Enclosure

15252

Indoor/Outdoor

NEMA 3R-Rated Enclosure

120VAC

277VAC (Default)

208~240VAC

NOTE: Unit is shipped with DIP Switches set for 277VAC Input Voltage.

CAUTION: Do not check circuits by “sparking” wires to terminals. Damage to

the timer may result.

INPUT VOLTAGE DIP SWITCH SETTING:
1. Do not apply power to the timer prior to setting correct Input Voltage DIP switch.
2. Determine the input voltage which will be applied to the timer (i.e. L1 and L2/N terminals,

see wiring diagrams).

3. Set the DIP Switch according to the diagram below.

Advertising