Functions
Reach setting (Control Pro Ultrasonic and
Dual tech sensors only)

Ultrasonic coverage can be selected from
minimum, 1/3, 2/3, or maximum by pressing
these buttons. Use this setting to increase or
decrease the coverage (detection range) of
the sensor.

Time setting CH 1 -
Stay 'ON' time for switching contact 1

The period of time you want the light to stay
'ON' for after last detecting movement can
be set from between 30 sec., 2 min., 5 min.,
15 min. and 30 min. by pressing these

buttons.

Setting the light to stay 'ON' for a time of your
own choice. Each press of the button incre-
ments the chosen time setting by 1 minute.

IQ mode. Stay 'ON' time is self-learning and
adjusts dynamically to user behaviour.
The optimum time is determined by means of
a learning algorithm. The shortest time is 2
min., the longest time 20 min.

Test mode. The test mode has the purpose of
checking for proper working order as well as
testing the detection zone. The presence de-
tector switches 'ON' for approx. 8 sec. re-
gardless of brightness and movement. The
test mode has priority over all other settings.
All user-selected potentiometer settings apply
in normal mode. The test mode ends auto-
matically after 10 min.

Time setting CH 2 -
Stay 'ON' time for switching contact 2 (HVAC)

The period of time you want the HVAC con-
tacts to signal the HVAC controller (stay 'ON')
after
last detecting movement can be set from 1
min., 5 min., 30 min., or 2 hours by pressing
these
buttons.

Light level setting

The chosen response threshold can be varied
from approx. 10 – 1000 lux / 1 - 100 fc.

Night-time mode (minimum setting
approx. 10 lux. , 1 fc.)

Daylight mode (maximum - light level function
overridden)

Teach-IN. Twilight setting at the memory but-
ton/Teach mode. This button must be pressed
at the level of light at which you want the sen-
sor to respond to movement. The current light
level is saved.

Sensor sensitivity (Ultrasonic and Dual tech only)

Ultrasonic sensitivity can be reduced by
pressing the button . The button re-

stores normal sensitivity. Use this setting to
adjust the amount of motion required within
the detection area
before the sensor will trigger.

Reset

Resets all settings to the values selected on
the detector manually or to the factory set-
tings.

4

1

3

2

6

5

7

8

9

10

11

12

1

2

8

9

3

4

Description
The RC 3 service remote (commissioning tool)
gives the installer the ability to set basic
functions of the entire line of Control Pro
sensors via remote control. Each valid press of
a button is indicated by a blue LED flash on the
sensor.

Advertising