CMP PX2KX/MF User Manual

Cable gland types

Advertising
background image

INSTALLATION INSTRUCTIONS FOR

CMP CABLE GLAND TYPES PX2KW/M,

PX2KW/MF, & PX2KX/M, PX2KX/MF

FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP ARMOUR,

PLIABLE WIRE (PX2KX/M & MF) & SINGLE WIRE ARMOUR (SWA) (PX2KW/M & MF). FOR USE IN GROUP

I MINING LOCATIONS.

INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC

CM

P

Do

cu

m

en

tN

o.

FI

45

2

Is

su

e

3

01

/1

3

0518

Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

Tel: +44 191 265 7411 • Fax: +44 191 265 0581

E-Mail: [email protected] • Web: www.cmp-products.com

Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.

I, the undersigned, hereby declare that the equipment referred to herein conforms tothe ATEX Directive 94/9/EC and the following standards:-

EN60076-0:2009, EN60079-1:2007, EN60079-7:2007, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241-0:2004, EN61241-1:2004

Dr Geof Mood - Technical Director - (Authorised Person)

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

Ca

bl

e

Gl

an

d

Se

le

ct

io

n

Ta

bl

e

Logo’s shown for illustration purposes only. Please check certification for details

CABLE GLAND TYPES

CABLE GLAND TYPES

PX2KW/M & PX2KW/MF

PX2KW/M & PX2KW/MF

PX2KX/M & PX2KX/MF

PX2KX/M & PX2KX/MF

Cable

Gland

Size

Available Entry Threads

Minimum

Thread

Length

Maximum Diameter

Over Conductors &

Maximum Number

Of Cores

Overall Cable

Diameter

Pliable Wire or Tape

Armour Range

Armour Wire

Diameter

Across

Flats

Across

Corners

Ordering

Reference

PX2KX/M

(Brass

Metric)**

Ordering

Reference

PX2KW/M

(Brass

Metric)**

Standard

Option

Grooved Cone

(PX2KX/M & MF)

Stepped Cone

(PX2KW/M & MF)

Metric

NPT

NPT

Diameter

Cores

Min

Max

Min

Max

Min

Max

Max

Max

20S

M20

1/2”

3/4”

15.0

12.6

11

9.5

15.9

0.3

1.0

0.8

1.25

30.5

33.6

20SPX2KX1RA/M 20SPX2KW1RA/M

20

M20

1/2”

3/4”

15.0

12.6

11

12.5

20.9

0.4

1.0

0.8

1.25

30.5

33.6

20PX2KX1RA/M 20PX2KW1RA/M

25S

M25

3/4”

1”

15.0

17.5

38

14.0

22.0

0.4

1.2

1.25

1.6

37.5

41.3

25SPX2KX1RA/M 25SPX2KW1RA/M

25

M25

3/4”

1”

15.0

17.5

38

18.2

26.2

0.4

1.2

1.25

1.6

37.5

41.3

25PX2KX1RA/M 25PX2KW1RA/M

32

M32

1”

1-1/4”

15.0

23.6

59

23.7

33.9

0.4

1.2

1.6

2.0

46.0

50.6

32PX2KX1RA/M 32PX2KW1RA/M

40

M40

1-1/4”

1-1/2”

15.0

30.0

89

27.9

40.4

0.4

1.6

1.6

2.0

55.0

60.5

40PX2KX1RA/M 40PX2KW1RA/M

50S

M50

1-1/2”

2”

15.0

36.6

115

35.2

46.7

0.4

1.6

2.0

2.5

60.0

66.0

50SPX2KX1RA/M 50SPX2KW1RA/M

50

M50

2”

2-1/2”

15.0

41.0

115

40.4

53.1

0.6

1.6

2.0

2.5

70.0

77.0

50PX2KX1RA/M 50PX2KW1RA/M

63S

M63

2”

2-1/2”

15.0

47.9

140

45.6

59.4

0.6

1.6

2.0

2.5

75.0

82.5

63SPX2KX1RA/M 63SPX2KW1RA/M

63

M63

2-1/2”

3”

15.0

53.7

140

54.6

65.9

0.6

1.6

2.0

2.5

80.0

88.0

63PX2KX1RA/M 63PX2KW1RA/M

75S

M75

2-1/2”

3”

15.0

59.9

140

59.0

72.1

0.6

1.6

2.0

2.5

89.0

97.9

75SPX2KX1RA/M 75SPX2KW1RA/M

75

M75

3”

3-1/2”

15.0

64.3

140

66.7

78.5

0.6

1.6

2.5

3.0

99.0

108.9

75PX2KX1RA/M 75PX2KW1RA/M

90

M90

3-1/2”

3-1/2””

15.0

75.3

140

78.2

90.4

0.6

1.6

3.0

3.5

114.0

125.4

90PX2KX1RA/M 90PX2KW1RA/M

100

M100

4”

-

15.0

85.6

200

86.1

101.5

0.8

1.6

3.15

4.0

123.0

135.3

100PX2KX1RA/M 100PX2KW1RA/M

All dimensions in millimetres unless otherwise stated

** Codes shown are for PX2KW/M & PXWKX/M glands, for flange mounted glands amend the ordering references as follows - PX2KW/MF or PX2KX/MF add “F”

e.g. 20PX2KW1RA/MF, 20PX2KX1RA/MF

PX2KW/MF

PX2KX/MF

PX2KW/M

PX2KX/M

PX2KW/M & PX2KX/M

- PX2KW/PX2KX Gland for

Mining Applications

PX2KW/MF & PX2KX/MF

- PX2KW/M & PX2KX/M

Assembly with Flange Mount

Type MA/FT

TECHNICAL DATA

CABLE GLAND TYPE

: PX2KW/M, PX2KW/MF, PX2KX/M, PX2KX/MF

INGRESS PROTECTION

: IP66, IP67, IP68, Type 4X; Oil Resistant II

PROCESS CONTROL SYSTEM

: BS EN ISO 9001

: ISO/IEC 80079-34:2011

HAZARDOUS AREA CLASSIFICATION

GLAND

ATEX CERTIFICATION No

: SIRA 06ATEX1097X

ATEX CERTIFICATION CODE

:

IM2 Ex d I / Ex e I

IEC Ex CERTIFICATION No

: IEC Ex SIR.06.0044X

IEC Ex CERTIFICATION CODE

: Ex d I / Ex e I

MA/FT

ATEX CERTIFICATION No

: SIRA 09ATEX1034U

ATEX CERTIFICATION CODE

:

IM2 Ex d I Mb

IEC Ex CERTIFICATION No

: IEC Ex SIR.09.0024U

IEC Ex CERTIFICATION CODE

: Ex d I Mb

INSTALLATION INSTRUCTIONS

Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all

instructions before beginning installation.

SPECIAL CONDITIONS FOR SAFE USE

1. The cable gland ranges shall only be used where the temperature, at the point of entry, is in the following ranges:

-60°C to +100°C.

2. The cable glands cable are only suitable for fixed installations. Cables must be effectively clamped to prevent twisting and pulling.

3. The entry component threads may need additional sealing to maintain the ingress protection ratings as applicable to the associated

equipment to which it is attached.

ACCESSORIES

The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-

Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud

Advertising