CMP T3CDSPB User Manual

Cable gland types, Cable gland types t3cds & t3cdspb t3cds & t3cdspb

Advertising
background image

INSTALLATION INSTRUCTIONS FOR

CMP CABLE GLAND TYPES

T3CDS & T3CDSPB

CABLE GLAND FOR USE WITH SINGLE WIRE ARMOUR (SWA), WIRE BRAID, STRIP, AND TAPE ARMOUR

(T3CDSPB VERSION CAN ALSO BE USED ON CABLE WITH A LEAD SHEATH).

FOR USE IN HAZARDOUS LOCATIONS.

INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC

CMP TRITON

TM

CDS

TM

DELUGE PROOF CABLE GLAND FEATURING

COMPENSATING DISPLACEMENT SEAL SYSTEM.

CM

P

Do

cu

m

en

tN

o.

FI

40

8

Is

su

e

7

01

/1

3

0518

Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

Tel: +44 191 265 7411 • Fax: +44 191 265 0581

E-Mail: [email protected] • Web: www.cmp-products.com

Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.

I, The undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the

following standards:-

EN60079-0:2006, EN60079-1:2007, EN60079-7:2007, EN60079-15:2005, BS 6121:1989, EN50262:1989 (Amd 2001), EN61241-0:2004,

EN61241-1:2004

Dr Geof Mood - Technical Director - (Authorised Person)

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

Cable Gland Selection Table

Logo’s shown for illustration purposes only. Please check certification for details

**

Insert “PB” into the code for T3CDSPB glands e.g. 20T3CDSPB1RA

*

For IP67 & IP68 requirements the Overall Cable Diameter (minimum value) shown above should be increased by 1.0 mm to ensure complete compliance

CABLE GLAND TYPES

CABLE GLAND TYPES

T3CDS & T3CDSPB

T3CDS & T3CDSPB

Cable

Gland

Size

Available Entry Threads Thread

Length

metric

Cable

Bedding

Diameter

Overall Cable

Diameter

Armour Wire Diameter

Across

Flats

Across

Corners Protrusion

Length

Ordering

Reference

(Brass Metric)

**

Cable

Gland

Weight

(Kgs)

Standard

Option

Grooved Cone Stepped Cone

Metric

NPT

NPT

Min Max Min* Max

Min

Max

Min

Max

Max

Max

20S/16

M20

1/2"

3/4"

15.0

3.2

8.7

6.1

13.4

0.15

0.5

0.9

1.0

24.0

25.9

70.0

20S16T3CDS1RA 0.170

20S

M20

1/2"

3/4"

15.0

6.1

11.7 9.5

15.9

0.15

0.5

0.9

1.25

24.0

25.9

70.0

20ST3CDS1RA

0.170

20

M20

1/2"

3/4"

15.0

6.5

14.0 12.5

20.9

0.2

0.5

0.9

1.25

30.5

32.9

72.0

20T3CDS1RA

0.256

25S

M25

3/4"

1"

15.0

11.1 20.0 14.0

22.0

0.2

0.6

1.25

1.6

37.5

40.5

82.0

25ST3CDS1RA

0.384

25

M25

3/4"

1"

15.0

11.1 20.0 18.2

26.2

0.2

0.6

1.25

1.6

37.5

40.5

82.0

25T3CDS1RA

0.379

32

M32

1"

1 1/4"

15.0

17.0 26.3 23.7

33.9

0.2

0.6

1.6

2.0

46.0

49.7

85.0

32T3CDS1RA

0.560

40

M40

1 1/4"

1 1/2"

15.0

23.5 32.2 27.9

40.4

0.2

0.8

1.6

2.0

55.0

59.4

86.0

40T3CDS1RA

0.848

50S

M50

1 1/2"

2"

15.0

31.0 38.2 35.2

46.7

0.2

0.8

2.0

2.5

60.0

64.8

98.0

50ST3CDS1RA

1.055

50

M50

2"

2 1/2"

15.0

35.6 44.1 40.4

53.1

0.3

0.8

2.0

2.5

70.0

75.6

100.0

50T3CDS1RA

1.521

63S

M63

2"

2 1/2"

15.0

41.5 50.0 45.6

59.4

0.3

0.8

2.0

2.5

75.0

81.0

108.0

63ST3CDS1RA

1.750

63

M63

2 1/2"

3"

15.0

47.2 56.0 54.6

65.9

0.3

0.8

2.0

2.5

80.0

86.4

103.0

63T3CDS1RA

1.685

75S

M75

2 1/2"

3"

15.0

54.0 62.0 59.0

72.1

0.3

0.8

2.0

2.5

89.0

96.1

105.0

75ST3CDS1RA

2.345

75

M75

3"

3 1/2"

15.0

61.1 68.0 66.7

78.5

0.3

0.8

2.0

2.5

99.0

106.9

114.0

75T3CDS1RA

3.200

90

M90

3"

3 1/2"

24.0

66.6 79.3 76.2

90.4

0.4

0.8

3.15

3.15

114.0

123.1

140.0

90T3CDS1RA

5.100

100

M100

4"

4 1/2"

24.0

76.0 91.0 86.1 101.5

0.4

0.8

3.15

4.0

123.0

132.8

170.0

100T3CDS1RA

6.500

115

M115

4 1/2"

5"

24.0

86.0 98.0 101.5 110.3

0.4

0.8

3.15

4.0

133.4

144.1

210.0

115T3CDS1RA

7.000

130

M130

5"

6"

24.0

97.0 115.0 114.2 123.3

0.4

0.8

3.15

4.0

146.1

157.8

250.0

130T3CDS1RA

7.800

Dimensions are displayed in millimetres unless otherwise stated

LISTED MARINE SHIPBOARD

CABLE FITTING

31YM

29NX

TECHNICAL DATA

CABLE GLAND TYPE

: T3CDS / T3CDSPB

INGRESS PROTECTION

: IP66, NEMA 4X, DELUGE TO DTS01-01

PROCESS CONTROL SYSTEM

: BS EN ISO 9001

: ISO / IEC 80079-34:2011

HAZARDOUS AREA CLASSIFICATION

ATEX CERTIFICATION No

: SIRA 06ATEX1283X & SIRA 06ATEX4328X

ATEX CERTIFICATION CODE

:

II 2 GD Ex d IIC / Ex e II / Ex nR II / Ex tD A21 IP66

IEC Ex CERTIFICATION No

: IEC Ex SIR.07.0005X

IEC Ex CERTIFICATION CODE

: Ex d IIC / Ex e II / Ex nR II / Ex tD A21 IP66

CSA CERTIFICATION No

: CSA.02.310517X

CSA CERTIFICATION CODE

: Class I Div 2 Gp, A, B, C, D; Class II Div 2 Gp E, F, G; Class III

UL CERTIFICATION FILE

: E200163, E256367

UL CERTIFICATION CODE

: Class I, Zone 1, AEx e II; TYPE 4X, OIL RES II

INSTALLATION INSTRUCTIONS

Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions

before beginning installation.

SPECIAL CONDITIONS FOR SAFE USE

1. The glands ranges shall only be used on enclosures where the temperature, at the point of mounting, is in the range -60°C to +130°C.

2. When used with braided cable, the cable glands shall be used for fixed installations only. Cables must be effectively clamped to prevent twisting

and pulling.

3. When used in Group I applications, the equipment must only be mounted where the risk of mechanical impact is low.

ACCESSORIES

The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-

Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer

Advertising