CMP TC User Manual

Cable, Cable connector connector type type tc tc

Advertising
background image

ASSEMBLY FITTING INSTRUCTIONS

FOR INSTALLATION OF CMP CABLE

CONNECTOR TYPE TC

FOR TERMINATION OF TRAY CABLES, FLEXIBLE CORD, UNARMOURED AND WIRE BRAID CABLES FOR

USE IN HAZARDOUS LOCATIONS

INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC

CM

P

Do

cu

m

en

tN

o.

FI

41

1

Is

su

e

4

01

/1

3

0518

Registered Office: Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

Tel: +44 191 265 7411 • Fax: +44 191 265 0581

E-Mail: [email protected] • Web: www.cmp-products.com

Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.

I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the

following standards-

EN60079-0:20079, EN60079-1:2007, EN60079-7:2007, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241-0:2006, EN61241-1:2004

Dr Geof Mood - Technical Director - (Authorised Person)

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

Ordering Reference

(Std Thread)

Entry Thread

Min

Thread

Length

Cable Range

Insert

Cable Range

No Insert

Across

Flats

Across

Corners

Assembled

Length

Approx

Weight

Aluminium

(Ozs)

Aluminium

NP Brass

S. Steel

NPT

Option

Min

Max

Min

Max

TC-050A028

TC-050A028

TC-050A028

1/2”

-

0.78

0.13

0.28

-

-

1.20

1.30

0.79

1.94

TC-075A028

TC-075A028

TC-075A028

-

3/4”

0.80

TC-050A055

TC-050A055

TC-050A055

1/2”

-

0.78

0.26

0.41

0.41

0.55

1.20

1.30

0.79

1.69

TC-075A055

TC-075A055

TC-075A055

-

3/4”

0.80

TC-075A079

TC-075A079

TC-075A079

3/4”

-

0.80

0.47

0.61

0.61

0.79

1.48

1.60

0.98

3.17

TC-100A079

TC-100A079

TC-100A079

-

1”

0.98

TC-100A104

TC-100A104

TC-100A104

1”

-

1.98

0.67

0.85

0.85

1.04

1.81

1.95

0.98

3.88

TC-125A104

TC-125A104

TC-125A104

-

1-1/4”

1.00

TC-125A127

TC-125A127

TC-125A127

1-1/4”

-

1.00

0.92

1.10

1.10

1.27

2.05

2.21

1.18

4.94

TC-150A127

TC-150A127

TC-150A127

-

1-1/2”

1.03

TC-150A150

TC-150A150

TC-150A150

1-1/2”

-

1.03

1.22

1.37

1.37

1.50

2.36

2.55

1.26

6.00

TC-200A150

TC-200A150

TC-200A150

2”

1.06

TC-200A174

TC-200A174

TC-200A174

2”

-

1.06

-

-

1.40

1.74

2.95

3.19

1.26

8.64

TC-250A174

TC-250A174

TC-250A174

-

2”

1.57

TC-200A197

TC-200A197

TC-200A197

2”

-

1.06

-

-

1.63

1.97

2.95

3.19

1.65

8.29

TC-250A197

TC-250A197

TC-250A197

-

2-1/2”

1.57

TC-250A220

TC-250A220

TC-250A220

2-1/2”

-

1.57

-

-

1.86

2.20

3.54

3.82

1.65

13.58

TC-300A220

TC-300A220

TC-300A220

-

2-1/2”

1.63

TC-250A244

TC-250A244

TC-250A244

2-1/2”

-

1.57

-

-

2.13

2.44

3.54

3.82

1.69

13.58

TC-300A244

TC-300A244

TC-300A244

-

3”

1.63

TC-300A268

TC-300A268

TC-300A268

3”

-

1.63

-

-

2.40

2.68

4.33

4.68

1.69

23.63

TC-350A268

TC-350A268

TC-350A268

-

3-1/2”

1.68

TC-350A315

TC-350A315

TC-350A315

3-1/2”

-

1.68

-

-

2.62

3.15

4.84

5.23

2.28

34.22

TC-400A315

TC-400A315

TC-400A315

-

4”

1.73

TC-400A354

TC-400A354

TC-400A354

4”

-

1.73

-

-

2.99

3.54

5.25

5.67

2.28

38.80

All dimensions in inches

Ca

bl

e

Co

nn

ec

to

rS

el

ec

tio

n

Ta

bl

e

Logo’s shown for illustration purposes only. Please check certification for details

CABLE

CABLE

CONNECTOR

CONNECTOR

TYPE

TYPE

TC

TC

TECHNICAL DATA

CABLE GLAND TYPE

: TC

INGRESS PROTECTION

: IP66, NEMA 4X

PROCESS CONTROL SYSTEM

: BS EN ISO 9001

: ISO/IEC 80079-34:2011

HAZARDOUS AREA CLASSIFICATION

ATEX CERTIFICATION No

: SIRA 09ATEX1092X

ATEX CERTIFICATION CODE

:

II 2 GD Exd IIC Gb / Ex e IIC Gb / Ex ta IIIC Da

IEC Ex CERTIFICATION No

: IEC Ex SIR.09.0042X

IEC Ex CERTIFICATION CODE

: Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da

cCSAus CERTIFICATION No

: CSA.09.2220601X

cSAus CERTIFICATION CODE

: Class I Div 2 Groups A, B, C, D; Class II, Div 2 Groups E, F, G; Class III Div 2; Enclosure type 4X;

Ex e ; Class I, Zone 1, AEx e

INSTALLATION INSTRUCTIONS

Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions

before beginning installation.

SPECIAL CONDITIONS FOR SAFE USE

• The glands shall only be fitted to enclosures where temperatures, at the point of mounting, is below 110°C.

• The cable shall be effectively clamped as close as possible to the gland.

• When used for Ex e (IP54) or Ex ta (IP6X) applications, the user shall provide a suitable interface seal between the gland and associated enclosure

to maintain the level of ingress protection.

• Under CEC Code Cable Glands with metric entry threads are only suitable for Areas Classified in ZONES unless fitted with an approved Metric to

NPT thread conversion adaptor. Under NEC Code, cable glands with metric threads can be used in divisions with the following restrictions:

• TC Cable Glands will be restricted to Hazardous Location Areas stated under the NEC/CEC Part I, Installation Code under WIRING METHOD.

• Gland Size 20S is for use with UL approved tray cable only.

ACCESSORIES

The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-

Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud *

Advertising