67 f, D 67, Specifications – Outback Power Systems GS4048A Operators Manual User Manual

Page 69: Table 16 radian inverter settings

Advertising
background image

Specifications

900-0161-01-00 Rev A

67

Table 16

Radian Inverter Settings

Field

Item

Default

Minimum

Maximum

(Gen Alert) OFF: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(Gen Alert OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Vent Fan) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(Vent Fan) Off Delay

0.5 minutes

0.1 minutes

25.0 minutes

(DC Divert) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(DC Divert ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(DC Divert) OFF: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(DC Divert OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(AC Divert) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(AC Divert ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(AC Divert) OFF: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(AC Divert OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

Inverter Stacking

Stack Mode

Master

Master, Slave

Power Save
Ranking

Mode = Master:

Master Power Save Level

0

0

31

Mode = Slave:

Slave Power Save Level

1

1

31

Grid-Tie Sell

Grid-Tie Enable

Y

Y or N

Sell Voltage

52.0 Vdc

44.0 Vdc

64.0 Vdc

Module Control

Module Control

GS8048A

Auto

Auto, Left, Right, Both

GS4048A

Left

Auto, Left, Right, Both

Calibrate

Grid AC Input Voltage

X

0 Vac

–7 Vac

7 Vac

Gen AC Input Voltage

X

0 Vac

–7 Vac

7 Vac

Output Voltage

X

0 Vac

–7 Vac

7 Vac

Battery Voltage

X

0.0 Vdc

–0.8 Vdc

0.8 Vdc

Grid Interface Protection Menu

Operating Frequency

Operating Frequency

X

60 Hz

50 Hz, 60 Hz

Stage 1 Voltage Trip

Over Voltage Clearance Time

X

1.0 seconds

0.12 seconds

5.0 seconds

Over Voltage Trip

X

132 Vac

120 Vac

150 Vac

Under Voltage Clearance Time

X

2.0 seconds

0.12 seconds

5.0 seconds

Under Voltage Trip

X

106 Vac

80 Vac

120 Vac

Stage 2 Voltage Trip

Over Voltage Clearance Time

X

0.16 seconds

0.12 seconds

5.0 seconds

Over Voltage Trip

X

144 vac

120 Vac

150 Vac

Under Voltage Clearance Time

X

0.16 seconds

0.12 seconds

5.0 seconds

Under Voltage Trip

X

60 Vac

60 Vac

120 vac

Frequency Trip

Over Frequency
Clearance Time

X

0.16 seconds

0.12 seconds

5.0 seconds

Over

Frequency
Trip

60-Hz system

X

60.5 Hz

60.1 Hz

65.0 Hz

50-Hz system

50.5 Hz

50.1 Hz

55.0 Hz

Under Frequency

Clearance Time

X

0.16 seconds

0.12 seconds

5.0 seconds

Under

Frequency

Trip

60-Hz system

X

59.3 Hz

55.0 Hz

59.9 Hz

50-Hz system

49.3 Hz

45.0 Hz

49.9 Hz

Mains Loss

Clearance Time

X

2.0 seconds

1.0 seconds

5.0 seconds

Reconnect Delay

X

300 seconds

2 seconds

302 seconds

Sell Current Limit

Maximum

Sell Current

GS8048A

X

30 Aac

5 Aac

30 Aac

GS4048A

15 Aac

5 Aac

15 Aac