Dc wiring, Installation – Outback Power Systems GS4048A Installation Manual User Manual

Page 22

Advertising
background image

Installation

20

900-0160-01-00 Rev A

DC Wiring

WARNING: Shock Hazard

Use caution when working in the vicinity of the inverter’s battery terminals.

CAUTION: Equipment Damage

Never reverse the polarity of the battery cables. Always ensure correct polarity.

CAUTION: Fire Hazard

The installer is responsible for providing overcurrent protection. Install a

circuit breaker or overcurrent device on each DC positive (+) conductor to

protect the DC system.

Never install extra washers or hardware between the mounting surface
and the battery cable lug. The decreased surface area can build up heat.

See the hardware diagrams on page 21.

IMPORTANT:

The DC terminals must be encased in an enclosure to meet NEC requirements.
The GS Load Center (GSLC) meets this requirement.

Table 4 contains OutBack’s recommendations for minimum cable sizes. Other

codes may supersede OutBack’s requirements. Consult local codes for final

size requirements.

Figure 15 GS8048A and GS4048A Battery Terminals

IMPORTANT:

The Radian GS8048A contains two internal power modules, each with its own

set of DC terminals. Both sets of terminals

must be connected to battery

power for the inverter to work correctly.

The Radian GS4048A contains a single power module which occupies the
space on the left. Although it has two pairs of terminals, only the pair on the

left is functional. The battery cables must be connected to these terminals.

The terminals on the right

must not be connected to battery power.

The Radian inverter has four battery cable terminals, two positive

and two negative. Each terminal is a threaded hole which accepts

a hex bolt (provided). Notes on assembly and cabling are shown

on the next page.

GS8048A

GS4048A