Parts Specifications:

NO. PART

MATERIAL


1

Nut

Stainless

Steel

2 Bushing Teflon
3

Cover

Cast

Iron

4

Seal

E.P.D.M.

5 Spherical

Flap St.St.SAE

304

6

Joint

St.St.SAE

304

7

Pin

St.St.SAE

304

8

Bolt and Nut

Galvanized Steel

9

Stem

St.St.SAE

304

10

Float

St.St.

SAE

304

11

Body

Steel

Din

ST.37

12

Ball Valve

Brass ASTM B124

B. Maintenance Procedure

 Before beginning the treatment, shut the gate valve underneath the air

valve.

 Release the bolts (8) and open the cover.

 Check if the rubber nozzle (4) is intact , wash and replace the nozzle if

torn.

 Check the spherical flap (5) and the float (10) and wash with clean

water.

 Check and wash with clean water the valve body (11) through the

upper cover.

 Open the flushing tap and drain the air valve.

 Wash the drainage elbow through which the air entered and

discharged the valve. This elbow attracts animals looking for humidity
like frogs, mice , etc.

 Reopen the gate valve.

st.

General

Routine maintenance of the valve is an integral part of
the right procedure for water system maintenance.
The servicing should be done once or twice a year
according to the quality and the kind of the liquids
flowing in the system.

K-020 KINETIC AIR VALVE FOR SEWAGE
MAINTENANCE INSTRUCTIONS

A.R.I

FLOW CONTROL ACCESSORIES

Hashikma Str. 17, Azur 58001 Tel.035588010 Fax.035589119