heater status Menu

This menu displays non adjustable operational information. Use the

Up & Down Buttons to navigate to the bottom of this menu.

top of Menu

bottom of Menu

status

Displays the current Operating State of the control system. IE:

Heating, Standby, Fault.

elements on #

Displays the number of heating elements the control system has

energized.

eco contact

Displays the current state of the ECO high temperature limit switch

contacts.

enable / disable 1 & 2

Displays the current state, open or closed, of the two Enable/Disable

circuits (J7 socket on the CCB - see wiring diagrams) provided

for external supervisory controls such as building EMS (Energy

Management System). Both of these Enable/Disable circuits must

be closed to “enable” heating operation. If either Enable/Disable

circuit is open for any reason heating operation will be “disabled.”

There is a plug with two jumper wires installed from the factory in the

CCB J7 socket to enable heating operation when external controls

are not in use.

Service Note: If a supervisory control(s) is used to enable/disable

heating operation, install field wiring between the J7 socket on

the CCB and a set of “dry contacts” on the external control per all

applicable building codes. This is a switching circuit only: DO NOT

apply any external voltage or connect any load (IE: relay coil) to

either circuit.

element # on

Displays the on/off status of each heating element. Yes = On, No =

Off.

tank full

Displays the status of the optional LWCO (Low Water Cut Off) device.

Yes = water level is acceptable, No = water level is low.

alarm condition

Displays the status of the user definable Alarm Output function - see

Alarm Output Setup Menu. Yes = alarm condition has been met, No

= alarm condition has not been met.

alarm relay output

Displays the state of the normally open contacts of the Alarm

Output relay. This relay (J3 contacts on the CCB - see wiring

diagrams) is used for building EMS (Energy Management

System) notification of operational conditions such as Fault

conditions.

econoMy Mode setup Menu

This menu contains settings used to establish an “Economy Set

Point” and “Economy Mode” operating periods. This control system

feature can help reduce operating costs during unoccupied, low load,

or peak demand periods.

desktop screen during economy Mode

economy Mode setup Menu

setpoint adjustment

Adjustable user setting (2°F to 50°F - factory default is

20°F) the control system uses to calculate the “Economy

Set Point.” The Economy Set Point = normal Operating Set

Point minus the programmed Setpoint Adjustment value.