Red Lion AIMI User Manual

Specifications, Description, Voltage drop at input

Advertising
background image

MODEL AIMI - 0 (4) TO 20 MA PASSIVE LOOP POWERED ISOLATOR

SPECIFICATIONS

1. INPUT RANGE: 0(4) to 20 mA
2. MAXIMUM INPUT CURRENT/VOLTAGE: 40 mA/18 VDC
3. VOLTAGE DROP AT INPUT: 1.7 V + (20 mA * RLOAD)
4. MAXIMUM INPUT FREQUENCY: <75 Hz
5. RESPONSE TIME: 5 msec. max.
6. OUTPUT SIGNAL: 0(4) to 20 mA

Max. Load Resistance:

 600 

7. ISOLATION VOLTAGE: 1.5 KV, 50 Hz, for 1 minute
8. ACCURACY:

0.1% of full scale

9. OPERATING TEMPERATURE RANGE: -20 to +65 °C
10. TEMPERATURE COEFFICIENT:

0.002%/K of the measured value

11. CONSTRUCTION: Case body is black, Polyester PBT
12. MOUNTING: Standard DIN style rail, including top hat (T) profile rail

according to EN50022 - 35

7.5.

13. WEIGHT: 2 oz (56 g)

DESCRIPTION

The AIMI0202 passive isolator is used for the electrical isolation and

processing of analog 0(4) to 20 mA standard current signals. The AIMI0202
provides electrical isolation between the control electronics and process I/O. In
addition, interference signals above 75 Hz are effectively suppressed.

Input and output circuit do not require separate auxiliary power. The

AIMI0202 obtains power from the input signal. The modules are snapped onto
symmetrical DIN rails in accordance with EN 50022.

VOLTAGE DROP AT INPUT

When using the AIMI0202, ensure the voltage supply is sufficient for

handling both the voltage drop of the input and the output load voltage drop. The
AIMI0202 input resistance will create around a 1.7 V drop.

The following formula calculates the total voltage drop (input and output).

Total voltage drop = (1.7 V + (20 mA * RLOAD))

Where:
1.7 V = Input voltage drop
20 mA * RLOAD = Output load voltage drop

WIRING CONNECTIONS

Connect transducer to input (Terminals 1 & 2), observing polarity. A power

supply may be required for loop powered transducers.

The energy for the supply on the input side is taken from the analog input

signal. Due to the dynamic input resistance, a power loss of approximately 1.7 V
drops at the module input. The module’s output is self-powered (active), which
is also derived from the input signal.

4

3

2

1

5

6

7

8

1

2

3

4

0.24 (6.2)

4.00

(102.5)

3.66 (93.1)

POWER

SUPPLY

LOOP-POWERED

TRANSDUCER

ISOLATED

INPUT

IN I (+)

GND1 (-)

(+) OUT I

(-) GND2

(-)

(+)

(+)

(-)

1

2

6

5

(+)

(-)

R

LOAD

DIMENSIONS In inches (mm)

ORDERING INFORMATION

IN I

GND 1

GND 2

OUT I

1

2

5

6

RLOAD

I

I

0 (4)-20 mA

0 (4)-20 mA

AIMI

OUTPUT

INPUT

MODEL NO.

AIMI0202

PART NUMBER

Bulletin No. AIMI-X
Drawing No. LP0824
Effective 11/09

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839

Red Lion Controls

China

Unit 101, XinAn Plaza

Building 13, No.99 Tianzhou Road

ShangHai, P.R. China 200223

Tel +86 21 6113-3688

Fax +86 21 6113-3683

Red Lion Controls

Europe

Printerweg 10

NL - 3821 AD Amersfoort

Tel +31 (0) 334 723 225

Fax +31 (0) 334 893 793

Red Lion Controls

India

54, Vishvas Tenement

GST Road, New Ranip,

Ahmedabad-382480 Gujarat, India

Tel +91 987 954 0503

Fax +91 79 275 31 350

Advertising