Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________
1/3/2011

Page 1 of 1










1

Specifications

Specifications

THM100

Number of Channels

4

Types Supported

J, K, T, R

J

-200 to +1200 °C

K

-200 to +1300 °C

T

-200 to +400 °C

Temperature

Range

R

0 to +1700 °C

Resolution

J,K,T

0.1°C

R

0.5°C

Full-scale

±0.2% full scale @ 25°C

Cold-Junction

±1°C

Accuracy

Temp. Coefficient

±100ppm/°C CJ (0-55°C)

Warm-up Time

15 minutes

Input Impedance

>10MΩ

Isolation

500V (backplane)

Dielectric Withstand

400Vac for 1 min (ch-ch)

Conversion Time

50mS/ch

Backplane Power Consumed

100mA @ 5V

External Power Required

100mA @ 24V (+/-10%)

Standard Terminal Type

Screw Type, Removable 11-posn

Optional Spring-clamp Plug

HE599TRM011

Storage Temp.

-25° to 70° Celsius

Operating Temp.

-0° to 55° Celsius

Relative Humidity

5 to 95% Non-condensing

Dimensions WxHxD

20mm x 90mm x 60mm

0.79” x 3.54” x 2.36”

Weight

63g (2.2 oz.)

CE & UL Compliance

CE, UL & C-UL


2

Wiring – I/O








3

Reported Data & Configuration Data


Data is reported to the OCS in signed integer format, with a single implied decimal place. For a
temperature of +762.4°C, with a data range configured for °C, the reported data value is 7624
decimal. For a temperature of -12.1°F, with a data range configured for °F, the reported data value
is -121 decimal.

The SmartRail THM100 is configured using Cscape (9.1 or later). The following parameters are
configurable for the THM100:

Cscape Configuration Data – Selectable per channel

Parameter

Selections

Enable

Channel Enable

Disable

K

J

T

Thermocouple Type

R

°C

Data Range

°F






4

Installation / safety






a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, thermocouple extension wiring of the proper type should be used for best
performance.
c. Shields should be terminated at one end only, at the end providing the best noise shunting.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:






7

Technical Support

Technical Support at the following locations:

North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]








THM100 LED Status Indication

LED

Meaning
ON = Normal Operation
FLASH = I/O Error

RUN

OFF = No Power or I/O Error
OFF = Normal Operation

ALARM

FLASH = Open Circuit Detected

SmartRail

Thermocouple Input Module (Type J, K, T, R)

HE599THM100

0.1°C Resolution, typical

No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.

Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

+

-

24VDC

N.C.

-

+

-

+

-

+

-

+

1

2

3

4

CH

+

_

24VDC @ 100mA
External Power

SHIELD GROUNDED
AT ONE END ONLY

+

_

+

_

+

_

+

_

Prefer Spring-clamps?

Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).