GENERAL


The GSM modem module supports the following features :

SMS

2

SMS FUNCTIONALITY

Up to 32 Send and 32 Receive messages with up to
20 Variables per message.

Group Names allow multiple devices to be grouped
together so that a particular message will be sent to a
number of different devices.

Phone number including country code and area code.
The phone numbers may have special characters
such as brackets, comma, plus and dash.

Register numbers can be used instead of phone
numbers. In this case, the phone number is stored in
PLC registers as ASCII data with a maximum size of
20 chars (10 words).

Bit, Byte, Word, Double Word and Real variable types
supported.

64-bit Status word includes communication status,
Initialization status, signal strength, invalid messages
count and Retry count for Init commands

160 character message buffer stores last sent or
received message.



















3

INSTALLATION / SAFETY























































WARNING

To comply with FCC RF exposure requirements, a separation distance of 20 cm (7.87”) or more must be
maintained between this antenna and all persons

Enfora certifies that the Enfora Enabler III-G ™ MHz GSM Radio Module (FCC ID: MIVGSM0308) complies with the RF hazard requirements
applicable to broadband PCS equipment operating under the authority of 47 CFR Part 22 or Part 24, Subpart E of the FCC Rules and
Regulations.

When found on the product,
the following symbols
specify:

Warning: Electrical
Shock Hazard.

Warning: Consult
user documentation.

WARNING: To avoid the risk of electric shock or burns,
always connect the safety (or earth) ground before making
any other connections.
WARNING: To reduce the risk of fire, electrical shock, or
physical injury it is strongly recommended to fuse the
voltage measurement inputs. Be sure to locate fuses as
close to the source as possible.
WARNING: Replace fuse with the same type and rating to
provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do not replace
the fuse again as a repeated failure indicates a defective
condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with
the construction and operation of this equipment and the
hazards involved should install, adjust, operate, or service
this equipment. Read and understand this manual and
other applicable manuals in their entirety before
proceeding. Failure to observe this precaution could result
in severe bodily injury or loss of life.
WARNING:

To

comply

with

FCC

RF

exposure

requirements, a separation distance of 20 cm (7.87”) or
more must be maintained between this antenna and all
persons.
WARNING: Maximum antenna gain is limited to 3 dBi* in
mobile products and applications. Maximum antenna gain
is limited to 7 dBi* in fixed products and applications.

All applicable codes and standards must be followed during
the installation of this product.

Adhere to the following safety precautions whenever any
type of connection is made to the module:

Connect the safety (earth) ground on the power
connector first before making any other connections.

When connecting to electric circuits or pulse-initiating
equipment, open their related breakers.

Do not make connections to live power lines.

Make connections to the module first; then connect to
the circuit to be monitored.

Route power wires in a safe manner in accordance with
good practice and local codes.

Wear proper personal protective equipment including
safety glasses and insulated gloves when making
connections to power circuits.

Ensure hands, shoes, and floor are dry before making
any connection to a power line.

Make sure the unit is turned OFF before making
connection to terminals.

Make sure all circuits are de-energized before making
connections.

Before each use, inspect all cables for breaks or cracks
in the insulation. Replace immediately if defective.