Horner APG SmartBlock HE-579ACM300 User Manual

1specifications

Advertising
background image

MAN0951-02

12 May 2011

PAGE 1

HE-579ACM300

Information is subject to change without notice.

The SmartBlock ACM300 is a Power and Energy Monitor that is easy to setup, and provides a variety of
advanced features, including:

• 3-phase Power Monitoring with three

current (0-5A CTs) and voltage inputs
(480V, direct connect or PTs).

• CsCAN CAN network connection

provides a fast flexible communication
path.

• SmartBlock package allows convenient

mounting close to the source to be
monitored

• On board relay allows load shedding,

alarming or other local switching.

1

SPECIFICATIONS

CURRENT INPUTS

VOLTAGE INPUTS

Conversion

True RMS

78.1K samples/sec

Conversion

True RMS

CT Input

5A Secondary

PT Input (or direct)

480V Secondary

Burden

0.2VA

Burden

2.0Mohm

Range

1 to 150% of CT Primary

Input Range

40 to 600Vac

Full Scale

150% of CT Primary

Full Scale

600Vac

Accuracy

<1% of Full Scale

Accuracy

Better than 1% full scale

RELAY OUTPUT (Form C)

Current

1A max at 30Vdc

0.5A max at 125Vac

Contact Voltage

30Vdc, Max

125Vac, Max

MEASURED DATA VALUES

Phase A RMS voltage (Va)

Watts (W)

Phase B RMS voltage (Vb)

Power Factor (PF)

Phase C RMS voltage (Vc)

Volt-Amps (VA)

Phase A RMS current (Ia)

Volt-Amps Reactive (VAR)

Phase B RMS current (Ib)

Kilowatt Hour (KWhr)

Phase C RMS current (Ic)

Voltage Peak (Vpeak)

Frequency (Hz)

Current Peak (Ipeak)

GENERAL SPECIFICATIONS

Required Power (Steady State)

40mA @ 24VDC

Required Power
(Inrush)

14A for 50uSec

Primary Power Range

10-30VDC

Operating Temperature

0 to +60 C

Relative Humidity

5 to 95%, Non-condensing

Measurement Rating

CAT III Max 600V

CONNECTIVITY

CAN Port

Horner CsCAN Peer-to-Peer

SmartBlock Power and Energy Monitor