TE525 Tipping Bucket Rain Gage

7.2.1 Pulse Count Example Programs

The following example programs use a pulse channel to read the output from
the rain gage. The CR1000 example will also work with the CR800, CR850,
CR3000, and CR5000. CR9000(X) programming is similar to the CR1000
except it has an additional parameter in the PulseCount() instruction to specify
the pulse module’s slot.

7.2.1.1 CR1000 Example Program

'CR1000
'TE525/TE525WS & TE525MM sample program

Public Rain_mm
Units Rain_mm=mm
DataTable(Rain,True,-1)

DataInterval(0,60,Min,0)
Totalize(1,Rain_mm,FP2,0)
EndTable


BeginProg

Scan(1,Sec,1,0)
'For TE525MM Rain Gage, use multiplier of 0.1 in PulseCount instruction
PulseCount(Rain_mm,1,1,2,0,0.254,0)

CallTable(Rain)
NextScan
EndProg

7.2.1.2 CR200(X) Series Example Program

'CR200(X) Series

'Declare Variables and Units
Public Rain_mm

Units Rain_mm=mm

'Define Data Tables
DataTable(Rain,True,-1)
DataInterval(0,60,Min)

Totalize(1,Rain_mm,0)
EndTable

'Main Program
BeginProg
Scan(1,Sec)

'TE525/TE525WS Rain Gage measurement Rain_mm:
PulseCount(Rain_mm,P_SW,2,0,0.254,0)
'Call Data Tables and Store Data

CallTable(Rain)
NextScan

EndProg

'For TE525MM Rain Gage, use multiplier of 0.1 in PulseCount instruction