APPLICATION NOTE

AN 147 FAN FAILURE SAFETY
LOCK-OUT CIRCUIT
“Field Provided”

EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 732-446-3110 FAX 732-446-5362

.

.

.

.

.

R

W

G

Y

TYPICAL

THERMOSTAT

R

W

G

Y

C

FURNACE

HUMIDISTAT

G1

R

G2

H

H

S2000 & S2020 HUMIDIFIER

NO

NO

NC

C

FAN FAILURE SAFETY LOCK-OUT CIRCUIT

SEPARATE

SAIL SWITCH

OR

CURRENT SENSING

RELAY CONTACTS

SPDT

K1 Interlock

Basic RELAY

24 VAC COIL

The use of a safety lock-out circuit is highly recommended. The circuit below is effective at
stopping the humidifier operation if the fan motor fails for any reason. The use of a system
interlock is optional and not required for basic operation. Failure to incorporate a lock-out
can result in excessive condensation inside the duct work and/or possible flood damage,
if the HVAC Fan/Blower fails to operate. This solution is provided as a supplement. Flood or
water damage as a result of not using this diagram is not the responsibility of EWC Controls.

K1 COIL

K2 COIL

SPST

K2 Interlock

Optional RELAY

24 VAC COIL