RDM-INC50 Incandescent Dimmer Module

6000 W

The RDM-INC50 Incandescent Dimmer Module is a standard 6000 W
incandescent dimmer. It can dim incandescent lights, cold-cathode, neon
transformers and two-wire dimmable ballasts. It is designed for use with the
RDA series of enclosures, in a AMX Lighting™ modular digital dimming
system. The RDM-INC50 module's 120, 240, and 277 VAC ratings are CE,
UL, and C-UL approved.

RDM-INC50 UL and C-UL Ratings

120 VAC, 6000 W

240/277 VAC, 6000 W

Suggested Dimmed Loads

Incandescent

Low-voltage

Neon, cold cathode

Two-wire, phase-controlled ballast

Specifications:

Dimensions (HW): 10.0" x 5.50" (25.4 cm x 13.97 cm)

Phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 16 in-lbs. (1.84 N/M)

Max. wire size: 8 AWG (10 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 7.0 lbs. (3.175 kg)

BTU/hr: 750

Control current: 45 mA @ 12 VDC

Occupies two enclosure spaces

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Run all control and low-voltage wires away from heat producing parts

of the dimmer.

Each dimming circuit must have a separate neutral connection.

Use low-voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

AC lighting loads only.

For indoor use only.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-INC50 to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-INC50

Line in (hot)

Load out

500µS choke

50 A Power
Device

Mounting
points

Low-voltage control
wiring: 4-pin connector
to AMX Lighting
master controller

FIG. 2 RDM-INC50 connections

FIG. 3 RDM-INC50 wiring application

Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)

RDM-INC50 4-pin module connector

4-pin plug from a RDM series module

Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).

2 (-)

1 (+)

Neutral

Load

Neutral

Load

Neon lights

(cold-cathode, on/off)

Two-wire

dimmable ballast

Neutral

Line in (HOT)

Load

All neutrals are common to the
Neutral block in the enclosure.
Provide a separate neutral for
each load.