Use this air conditioner under the following temperature range
(CU-E10HBEA)

Temperature (°C)

Indoor

Outdoor

*DBT

*WBT

*DBT

*WBT

COOLING

Maximum

32

23

43

26

Minimum

16

11

-10

-

HEATING

Maximum

30

-

24

18

Minimum

16

-

-10

-

NOTICE: • This unit is still able to operate as a cooler with outdoor temperature as low as -10°C in a non-living room, such

as a computer room, with a room temperature of 16°C or above, and room humidity up to 80%. When the

outdoor temperature drops to -10°C, compressor will be cut off and resume operation again once the temperature

rises to more than -10°C.

• When the outdoor temperature is out of the above temperature range, the heating capacity will drop signifi cantly

and outdoor unit might stop for protection control.

(CU-2E15LBE, CU-2E18LBE, CU-4E27CBPG)

Temperature (°C)

Indoor

Outdoor

*DBT

*WBT

*DBT

*WBT

COOLING

Maximum

32

23

43

26

Minimum

16

11

16

11

HEATING

Maximum

30

-

24

18

Minimum

16

-

-10

-11

(CU-3E18LBE, CU-4E23LBE)

Temperature (°C)

Indoor

Outdoor

*DBT

*WBT

*DBT

*WBT

COOLING

Maximum

32

23

46

26

Minimum

16

11

-10

-

HEATING

Maximum

30

-

24

18

Minimum

16

-

-15

-16

* DBT: Dry bulb temperature
* WBT: Wet bulb temperature