Atlas Sound APF-15TUC User Manual

Installation instructions, Wiring diagram, Speaker 1 speaker 2

Advertising
background image

WIRING DIAGRAM

To conform with UL requirements, wires must be connected as shown in wiring diagram.

NOTE: The maximum wire size that can be connected to this device is 18 Gauge!

Speaker 1 Speaker 2

CAUTION: Do Not loop wires under screw terminals. Break wire run to provide supervision of connection.

Installation must comply with all Building Codes and NFPA guidelines. Installation must adhere to N.E.C.

and NFPA 70/72 wiring directives and comply with all National and Local Building Codes.

APF-15U, APF-15TU, APF15TUC

INSTALLATION INSTRUCTIONS

Specifications are subject to change without notice

www.AtlasSound.com

1601 JACK MCKAY BOULEVARD ENNIS, TEXAS U.S.A. • TELEPHONE: (800) 876-3332 • FAX: (800) 765-3435

© 2005 ATLAS SOUND LP

Printed in U.S.A.

000105

ATS000702 RevE 01/05

PN 8840400

GENERAL DESCRIPTION

• Atlas Sound Models APF-15U, APF-15TU and APF-15TUC are high efficiency, U.L. Listed double re-entrant type loud
speakers. They comply with the requirements of UL Standard 1480, Fire Protective Signalling Speakers.
• They are designed to be used in conjunction with compatible control equipment for high intelligibility reproduction of
audible emergency and protective signals as well as voice messages.
• Model APF-15TUC includes a supervisory capacitor and is suitable for installation in systems employing supervised
circuitry (25V/70.7V). Maximum supervised circuit voltage is 24 VDC.
• For use in ambient ranges from -40˚C to 66˚C.

SPECIFICATIONS

POWER: 15 Watts RMS

FREQUENCY RESPONSE: 400-4,000Hz

SOUND LEVEL: 103dB UL 10' Rating

(APF-15U Only)

CONDUIT CONNECTION: For

1

2

" Conduit

Mounting Dimensions

To Next Speaker
or End of Line
Resistor

Power Tap Selector Switch

Switch

Impedance

25V

*db@

70V

*db@

Position

Line

10 Ft.

Line

10 Ft.

1

5.0 K

-

.9 W

90

2

2.5 K

-

1.8 W

93

3

1.3 K

.48 W

87 3.8 W

95

4

666

.94 W

90 7.5 W 98

5

333

1.8 W

93 15.0 W

100

6

89

7.5 W

98 Do Not Use

7

45

15.0 W

100 On 70 V.

* UL 3dB Increment Rating

6.12"

(155.5mm)

NOTE: Terminal #2 is the positive terminal

UL

CL

ASSIFIED

R

From
Amplifier

Advertising
This manual is related to the following products: