Quick Start Guide

1

Make sure that the panel(s) have

been wired by a certifi ed electrician

and that there is power to the

panel(s).

Confi rm that RPS (slave) panels

are connected to the master as

indicated in the “RPC to RPS Wiring

Instructions” bulletin.

2 Confi rm that the electrician has

connected the 15A breaker in the

master panel (position 21) to the

power supply in the lower sidecar.

3 Once the 15A breaker is connected

and switched on, confi rm that the

orange power LEDs on each circuit

board are lit.

Control Board

I/O Expander

Board

Multi-Panel Expander

Board

POWER LEDS

If LEDs do not light, check chapter

4 of the RPC manual to see that

circuit boards are connected

properly.

4 Connect a computer to the control

board using a CAT5 crossover

cable OR connect the RPC to your

network.

If connecting via a crossover cable:

With a computer directly connected

to the RPC through the Ethernet

port, change the computer’s IP

address manually so it is in the same

default IP subnet that the RPC uses:

192.168.1. The default IP address of

the RPC is 192.168.1.250.

Ethernet Port

Yellow

Buttons

LCD

Screen

If connecting via a network:

Connect the RPC to the network via

the Ethernet port. Push the upper

yellow button twice or until the IP

address appears on the LCD screen.

OVER

Panel Neutral Bus

Panel Ground Bar

Power Supply DC –

Controller Cable

Controller Cable

Power Supply DC +

N L

+ + – –

Transducer Neutral

Transducer Load

15A Breaker

139-0522-00 RPC Quicksheet