NOVUS TP694 User Manual

Electromagnetic compatibility

Advertising
background image

694

Operating instructions
Pressure, vacuum, differential pressure transmitter

Warning
Please read the operating instructions carefully
before commissionning the pressure transmitter.
The guarantee is invalid in respect of damage re-
sulting handling or inappropriate use. We accept
no responsibility for consequential damages
resulting from any ot the above.
The device must be installed and dismantled
only by qualified personnel.
The relevant country-specific harmonised sa-
fety regulations must be observed.
The customer must ensure compliance with
device-specific reguirement relating to the
protection standard.

Factory setting
Pressure 0, output signal < 100 µA or 4 mA or
< 50 mV at voltage output.
Maximum pressure = maximum output signal.

Adjustable version
Attention: Only versions whose product numbers
have the following digits at the 5th and 6th
place after the dot can be calibrated:
694.9XXX21(23/24/25/31/35)XXX.
(ZP not adjustable.)

with square

linear

root extraction

Full scale adjustable with
potentiometer from 40 % to
100 %.

Recommendet installation
arrangement: vertical, with
pressure connections facing
downward
(factory calibration).

Horizontal, cover facing down-
ward. Signal approximately
10 Pa higher than actual pres-
sure.

Horizontal, cover facing up-
ward. Signal approximately
10 Pa below than actual pres-
sure.

2-wire

3-wire

Electromagnetic compatibility

Type of interference

Test standard

Effects

Electrostatic discharge ESD

EN 61000-4.2

no failure (criterion B)

8 kV air discharge / 4 kV contact discharge

High-frequency electromagnetic

EN 61000-4-3

no effect (criterion A)

radiation (HF)

0.15 … 80 MHz, 10 V/m

Fast transients (Burst)

EN 61000-4-3

no failure (criterion B)

± 2 kV

EN 55022

Conducted interference

0.15 ... 30 MHz

no effect

Radiation from housing

30 ... 1 000 MHz

no effect