Pathway DMX Relay Controller (programmable) - # LCRC48GEP User Manual

Lcrc48gep dmx relaycontroller configuration, Installation instructions, Dip switch settings

Advertising
background image

LCRC48GEP DMX RELAYCONTROLLER Configuration

INSTALLATION INSTRUCTIONS

1 - Ensure that relay panel power is off (no indicator LEDs

glowing on the system motherboard). Remove the metal
cardframe cover.

2 - Connect the DMX data line at the panel motherboard, with D-

to the black terminal and D+ to the red terminal. Attach the
shield drain wire to the SHIELD terminal.

3 - If the DMX line is to be passed through to another panel,

attach the outgoing wires to the second set of data terminals.

4 - If the relay panel is the last panel on the DMX wire run, it is

recommended that a 100 or 120 ohm 1/4W termination
resistor be installed between one pair of black and red data
line terminals.

5 - Connect switch wiring to the A/B master switch input terminals

as required. The white terminal is switch common, the red is
switch "on", and black is switch "off". Connect the pilot lamp to
the yellow terminal adjacent to the first of the assigned relays.

6 - Plug the controller card and one to four LCRD-12 driver cards

firmly into the cardframe.

7 - Configure the controller card according to the following DIP

switch settings. Restore power.

8 - Check that the power LED (between the DIP switch and the

three rotary switches) is glowing steadily. This indicates +5
volts present and correct microprocessor operation. A flashing
LED indicates a defective controller card.

9 - Follow the program mode instructions to program the card for

optional DMX patch assignment and panel master switch
inputs.

10- Apply the DMX control signal and observe that the receive

data LED (at left) is glowing. The LED will not glow if the
address set on the rotary switches exceeds either 512 or the
number of dimmer signals present on the data line, if the data
format does not conform to USITT-DMX512, or if the data
wires are reversed at the mother board.

11- Verify relay operation with the DMX control system or the

card's test function, then use the checklist to ensure that
everything is set correctly before re-installing the cardframe
cover.

THRESHOLD SELECT

DS-1

25% THRESHOLD (Trigger on at 30%, off at 20%)

ON

75% THRESHOLD (Trigger on at 80%, off at 70%)

OFF

STATUS QUO

DS-2

ON (INFINITE HOLD)

ON

OFF (2 SECOND HOLD)

OFF

RELAY SELECTION

DS-3

DS-4

1-12 RELAYS INSTALLED

ON

ON

13-24 RELAYS INSTALLED

OFF

ON

25-36 RELAYS INSTALLED

ON

OFF

37-48 RELAYS INSTALLED

OFF

OFF

CONTROL MODE

DS-5

PATCH
Addressing determined by programmed patch for
each relay

ON

OFFSET
Panel start address determined by the address
select switches

OFF

SCAN RATE

DS-6

FAST SCAN (50 msec., 20 relays per second)

ON

NORMAL SCAN (100 mseC., 10 relays per second)

OFF

DIP Switch Settings

3.7"

10.3"

JP1

OPEN POSITION SHOWN

J1

RxD

x100

x10

x1

PWR

ADDRESS SELECT

RELAY SELECT

PROGRAM

DS

ON=DOWN

PGM TST

x1

S1

x10

PROGRAM MODE

DS-7

Program Mode Enabled

ON

Program Mode Disabled (RUN MODE)

OFF

TEST MODE

DS-8

Test Mode enabled

ON

Normal (RUN) Mode

OFF