Pathway Programmable Relay Driver -# LCRD16 User Manual

Lcrd16 relay driver, Configuration, Connector legend

Advertising
background image

LCRD16 RELAY DRIVER

CONNECTOR J1

RPWR1 Relay Coil Power Supply (Hot), 24VAC

RPRW2 Relay Coil Power Supply (Neut.), 24VAC

CP

Control Power Supply 12-24VAC or DC(+) 200mA

CC

Control power supply common

CC

Control power supply common

D+

DMX512 Data +

D-

DMX512 Data -

SH

DMX512 Shield

CONNECTOR J2

A-ON

Master Switch “A“ input, momentary ON

A-OFF

Master Switch “A” input, momentary OFF

B-ON

Master Switch “B” input, momentary ON

B-OFF

Master Switch “B” input, momentary OFF

COM

Master Switch common (4 positions)

CONNECTOR J3-J6

1A/B

thru

16A/B

Relay coil drive outputs, one coil drive wire each for
momentary polarized pulse-latching relays and AC

maintained coil relays (“A” lead); one coil common
wire per relay (“B” lead)

CONNECTOR LEGEND

NOTE: Relay coil drive maximum rating 300mA continuous, 3A
surge (inrush). Use a pilot relay for higher current requirements.

RELAY TYPE

DS-1

Momentary: Outputs a 100ms polarized DC pulse
for 2-wire latching relays

ON

Maintained: Outputs a constant AC voltage for
maintained relays

OFF

THRESHOLD SELECT

DS-2

25% Threshold (on at 30%, off at 20%)

ON

75% Threshold (on at 80%, off at 70%)

OFF

OUTPUT SCAN MODE

DS-3

Scan Mode Enabled:
Turns relays on or off in sequence, 10 per second

ON

Scan Mode Disabled:
Turns relays on or off simultaneously

OFF

CONTROL MODE

DS-4

Patch:
Addressing determined by user programmed patch

ON

Offset:
Addressing determined by address select switches

OFF

PROGRAM MASTER SWITCH

DS-5

DS-6

Program Master Switch “A”

ON

OFF

Program Master Switch “B”

OFF

ON

PROGRAM MODE

DS-7

Program Mode Enabled

ON

Program Mode Disabled

OFF

TEST MODE

DS-8

Test Mode enabled

ON

Normal (Run) Mode

OFF

DIP Switch Settings

DS-7 must be OFF and DS-8 ON. The “TEST” LED will
be on.

Relay Test Function:
DS-4 must be off. The DMX
address switches select the relay number to test. The
selected relay can then be turned on by pressing the
program pushbutton. If the number is out of the correct
range (000 to 016 in momentary mode) the "TEST" LED
will flash to indicate an error when the button is pressed.
DMX Test Function: The DMX receive LED (RxD) will
be on and steady if a valid DMX signal is received. If no
DMX signal is present the LED will be off. If the DMX
signal is not valid the LED will flash continuously.
Patch Testing Mode: DS-4 must be on. The address
switches select the DMX channel #. When the program
pushbutton is pressed, relays assigned to that DMX
channel # will turn ON. When the pushbutton is released
those relays will turn OFF. The "TEST" LED will flash
once if there is an error in the address range selection.

TEST MODE

Configuration

PROGRAMMABLE WITH
MASTER SWITCH INPUTS

0.5000"

5.0000"

5.5000"

0

.25

00

"

7

.25

00

"

7

.50

00

"

Advertising