Automation Components ACI/592-10K-CS User Manual

Ac i, Installation and operation instructions

Advertising
background image

Installation and Operation Instructions

ACI/592, ACI/592-10K

ACI/592-CS, ACI/592-10K

-CS

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562

PH: (608) 831-2585 FAX: (608) 831-7407

II-19

A

C

I

utomation

omponents

nc.

READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION

All ACI/592 and ACI/592-10K semiconductor sensors are both polarity and non-position sensitive. All semiconductor

sensor type room units are supplied with a two or three pole terminal block depending on whether they have a current or

voltage output.

The following units are available with corresponding terminal blocks for all connections: Room with Setpoint (RS),

Room with Override (RO), Room with Setpoint and Override (RSO), and Room with Setpoint, Override, and RJ12

Communication Jack (RSO RJ12).

All other configurations are supplied with 22 gauge lead wires and can be hooked up with any crimp style or wire nut wire

connectors.

n

TROUBLESHOOTING

Sensor reads 0 uA or VDC

Check supply Voltage - Sensor or wires are shorted together open

Sensor reads supply voltage or high current Sensor or wires are shorted together

Erratic readings

Bad wire connections - Condensation or Moisture problem – RF Noise

n

WIRING DIAGRAMS

J2

Short Sensor

Separate Input

SW1

+ - SEN O/R SET

1 2 3 4 5 6

6

1

6 Pin RJ12

Communication Jack

Power Supply Common or

Ground

+15 VDC Supply Voltage

for Sensor

uA or VDC Sensor Output to

Controller or System

Tenant Override or Dry Contact Output

to Controller

(Separate Input Only)

Setpoint Resistance Output to Controller

(CS Version has a 2.732 to 3.332 VDC Output)

Terminals for RJ12 Communications

J3

Membrane

Wire Access Hole

“After Hours” Normally-Open

Override Switch

Override Shorts

Separate Input

Sensor

(Dry Contact Closure

)

Figure #1

Override Options Jumper Settings (J3)

Short Sensor

Separate Input

Short Sensor

Separate Input

**Note: All Room with Override (RO) and Room with Setpoint and Override (RSO) sensors are shipped with the

Override in parallel with the sensor unless specified otherwise. If a separate Input or Tenant Override is

Needed, see Figure #1 for the Override Options jumper Settings.

** NOTE: (J2) is only used for Connection of the Membrane Switch.

CSI Rev 7