Automation Components A/RH-LCD Series User Manual

A/rh-lcd series, Figure # 1, Installation and operation instructions

Advertising
background image

Installation and Operation Instructions

A/RH-LCD Series

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562

PH: (608) 831-2585 FAX (608) 831-7407

www.workaci.com

I0000150 Rev 4

Page 1 of 4


Please Read Instruction Carefully Before Installation!

Wiring Connections

ACI recommends that all A/RH-LCD humidity transmitters be wired with 16 to 22 AWG shielded wire for best
results.

+24 VAC Input Wiring Diagram


24 VAC
Secondary

120 VAC

Primary

PLC or HVAC
Control System

AI1 AI2 AI3 AI4

Analog Inputs

Analog Input

Common

-

-

Optional 250 Ohm or
500 Ohm Load Resistor
for a 1 - 5 or 2 - 10 VDC
Output.

A/LCD-R 4-20 mA

(Loop Powered LCD Indicator)

A/RH Transmitter
+24 VAC Input / 4-20mA Output

10 Pin LCD Socket

24 VAC Supply Common

RH 4-20 mA Output

+24 VAC Supply Voltage

RH 4-20 mA Output
to Controller

Optional Temperature
Sensor Output
to Controller (Resistive)

TTRO LCD Rev 7

- TEMP +

- LCD +

ZERO

SPAN

Factory Use Only

8

7

6

5

1

3

2

4

ON

Push tab in and pull up on the sensor
cable to remove from J13 connector

Figure # 1