InRow RD 10 kW Air Cooled Operation and Maintenance

42

Mechanical

Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform
Lockout/Tagout procedures before performing any electrical or mechanical service. Wear
appropriate personal protective equipment when checking hazardous voltages.

‰ Check the fans. All components should be moving freely with no signs of binding or damages.

‰ Verify that the condensate line is flowing freely.

Electrical

Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform
Lockout/Tagout procedures before performing any electrical or mechanical service. Wear
appropriate personal protective equipment when checking hazardous voltages.

‰ Inspect the electrical panel for tight connections and for overheated connections from loose contact

terminals.

‰ Confirm that the incoming main power matches the rating listed on the nameplate of the cooling unit. The

measurement should be within 10% of the nameplate listing.