Aube Technologies TH150 Series User Manual

Th150 series, Introduction, Installation

Advertising
background image

TH150

400-150-000-C 5/9/06 1/6

1. Introduction

The TH150 Series electronic thermostat is designed for low-voltage
pressure-dependent variable air volume (VAV) applications. It
comes in four different models:

Depending on the model, the TH150 thermostat can have up to
three outputs connected to the following control devices:



actuators



thermal valves (N.O. and N.C.)



solenoid valves



solid-state relays (SSRs)



silicon-controlled rectifiers (SCRs)



mechanical relays



contactors

Accessories



RC840 or RC840T electromechanical relay



RT850 or RT850T solid-state relay



AC146-410 temperature sensor



AC144-03 temperature sensor

2. Installation

2.1 Mounting Instructions

n

Remove the thermostat from its base by unscrewing the cap-
tive screw and tilting the bottom of the thermostat up. The
screw cannot be completely removed.

o

Pass the wires through the center hole of the base and secure
the base to the wall or onto an electrical box.

p

Wire the thermostat. See section 2.2 for terminal designations
and section 3 for typical wiring diagrams.

q

Reinstall the thermostat onto its base and secure with the cap-
tive screw.

2.2 Terminal Designations

The designations of the terminals vary according to the particular
model of thermostat. Refer to the following table for the description
of each terminal.

• TH150-1A

• TH150-1F

• TH150-1A2T

• TH150-1F2T

Configuration and status display

Heating mode

Temperature display

Output power display

Temperature
adjustment
button

Cooling mode

Override button

TERMINAL

DESCRIPTION

1
2

24 VAC
COM

Power supply

3
4

AN1
COM

Output 1

Models TH150-1A and TH150-1A2T

3
4

OPEN
CLOSED

Models TH150-1F and TH150-1F2T

5
6

T2/AN2
T2/COM

Output 2 (models TH150-1A2T and TH150-1F2T)

7
8

T3
T3

Output 3 (models TH150-1A2T and TH150-1F2T)

9

10

COM
SENSOR

External sensor input. (For applications requiring
an external sensor, see section 4.2.)

9

11

COM
C-Over

Mode Changeover input (N.O. contact). See sec-
tion 5.5.2.

9

12

COM
NSB

Night Setback activation input (N.O. contact).
See section 5.6.

Note

: To configure the terminals, see section 4.

TH150 Series

Installation and User Guide

VAV Thermostat