The furnace must have a 115-v power supply properly connected
and grounded. Proper polarity must be maintained for correct
operation. Thermostat wire connections at R, W, C, and Y must be
made at the 24-v terminal block on the furnace control. The gas
service pressure must not exceed 0.5 psig (14-in. wc), but must be
no less than 0.16 psig (4.5-in. wc).

Fig. 10—Furnace Control

A00292

G

R

Y

W

Com

24V
HUM

3-AMP FUSE

HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)

LED OPERATION &
DIAGNOSTIC LIGHT

HARNESS CONNECTOR

24-V TRANSFORMER SEC-2

SPARE-1

SPARE-2

EAC-1 (BLACK)

EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1 AMP MAX)

EAC-2 (WHITE)

115-VAC (L2) NEUTRAL
CONNECTION

24-V THERMOSTAT
TERMINALS

BLOWER SPEED
SELECTION TERMINALS

INDUCER MOTOR
CONNECTOR

115-VAC (L1)

POWER SUPPLY

HOT SURFACE

IGNITOR CONNECTOR

HEAT

COOL

BLOWER OFF DELAY
ADJUSTMENT SWITCH

SEC-1

TEST/TWIN

Fig. 9—Heating and Cooling Application Wiring Diagram

A98209

115-V

FIELD-SUPPLIED

DISCONNECT

AUXILIARY
J-BOX

CONTROL

BOX

24-V

TERMINAL

BLOCK

THREE-WIRE

HEATING-

ONLY

FIVE

WIRE

NOTE 1

NOTE 2

FIELD-SUPPLIED
DISCONNECT

CONDENSING
UNIT

TWO
WIRE

FURNACE

R

G

C

W

C

R

G

Y

GND

GND

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING

208/230- OR
460-V
THREE
PHASE

208/230-V
SINGLE
PHASE

WHT

BLK

WHT

BLK

NOTES:

Connect Y-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.

W

Y

GND

THERMOSTAT
TERMINALS

1.
2.
3.

—10—