Hale FoamLogix 2.1A-LF Low Foam Flow Calibration User Manual

Quick start guide, Foamlogix 2.1a-lf low foam flow calibration), Calibration

Advertising
background image

Quick Start Guide

(FoamLogix 2.1A-LF Low Foam Flow Calibration)

1. If not already attached, connect a hose

to the barbed fitting located on the 3-way

bypass valve on the foam pump/motor

assembly.

2. Place the hose into a clean calibrated

measuring container to confine the

discharged foam. The original 5 gallon

foam container works well.

3. Turn the bypass valve handle so that the

ARROW points in the direction of the

barbed fitting (foam flows out the bypass).

4. Make certain the FoamLogix display

is showing the water flow rate screen

(“FLOW” LED is ON). If not, press the “i”

button until the water flow rate screen is

shown.

5. Put the FoamLogix display into

simulated water flow by pressing the UP

ARROW and DOWN ARROW buttons

simultaneously.

English Units

The FoamLogix display should show

“S

150” or less (Simulated flow, 150 gpm).

Metric Units

The FoamLogix display should show

“S 567” or less (Simulated flow, 567 lpm).

If not, use the UP/DOWN arrow buttons

to adjust the value.

6. Press the “i” button once on the Foam

Logix display to show the foam rate

percentage screen (“%” LED is ON). Use

the UP/DOWN ARROW buttons to set the

foam flow percentage to 0.1%

7. Press the ON/OFF button on the Foam

Logix display. The system will begin

flowing foam. Press the ON/OFF button

after 10 seconds to stop the foam flow.

8. Press and hold the DISPLAY button (

i

)

on the FoamLogix display until PASS is

shown – approximately 2 seconds. (See

Figure 1.)

9. With the DISPLAY button (

i

) pressed,

press the INCREASE button 4 times

( ). (See Figure 2)

A u is shown with each INCREASE

button press.

10. Release the DISPLAY button (

i

). The

display shows CAL for about 2 seconds

indicating the calibration mode is

entered.

11. Press the DISPLAY button (

i

) 4 times

until A 0.00 is shown. (See Figure 3 on

the next page.)

12. Press the red ON/OFF button ( ). The

bar graph illuminates 7 bars, the foam
motor begins running, and the display
value starts increasing. (See Figure 4 on
next page.)

Calibration

Figure

2

THIS QUICK START GUIDE IS ONLY INTENDED AS A BRIEF OVERVIEW TO THE

OPERATION OF THE FOAMLOGIX 2.1A-LF SYSTEM AND IS NOT INTENDED TO

BE A REPLACEMENT FOR THE CURRENT INSTALLATION/OPERATION MANUAL

(029-0021-74-0) PROVIDED WITH EACH SYSTEM.

ALSO AVAILABLE ON-LINE – WWW.CLASS1.COM.

Figure

1