Aerovent IM-120 User Manual

Im-120, Installation

Advertising
background image

CAULK

STACK

CAP

SECTION

STACK

CAP

SECTION

FAN

CURB BASE

CURB BASE

Model 53

Model 40C & SV40

©2007 Aerovent

Installation

1. Check for possible damage in shipment to roof ven-

tilator.

2. Assemble stack cap section, fan and curb base.

3. Caulk between flanges of damper section, fan section

and curb base (see illustration).

4. Install assembled ventilator onto roof curb. Secure

ventilator to curb with bolts (see illustration).

5. Check propeller for proper rotation.

6. Make certain dampers operate smoothly and are free

from obstruction.

Model 53, 40C and SV40 Roof Ventilators

Field Procedure: Caulk ventila-
tor at locations where indicated
to prevent leakage.

Detail of Mounting

Flat Type Curb Base on Existing Roof

Use Hydro Shield and heavy-duty glass mem-
brane — Addex Corporation (or equal).

1. Set ventilator curb base in mastic.
2. Apply mastic over curb base flange.
3. Work membrane into mastic.
4. Trowel mastic over membrane and work in

.

ROOF CURB

ROOF CURB

6" MIN.

4"

Flashing

Caulk

Seam

Caulk

Seam

New Roof

New Roof

Existing Roof

STD. CURB BASE

FLAT TYPE

CURB BASE

FLAT TYPE

CURB BASE

8" Min.

4"

Membrane

Mastic

Mastic

Existing

Roofing

Roof Structure

Ventilator

Base

General Installation, Operation and Maintenance Instructions For Aerovent Products