Model 70200

Universal Oil Primary Control

Tech Support (800) 989-2275

www.carlincombustion.com

Installing and wiring

WarningThe 70200 control must be installed and serviced only by a qualified service technician.

1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with applicable codes and

ordinances.

2. Thermostat terminals (T–T) provide a current source. Never apply external power to these terminals under any circumstances.

3. Alarm terminals provide a 24 VAC/VDC-rated dry contact, suitable for use with security/fire alarm systems.
Mounting

• The control may be mounted on a 4” x 4” junction box in any convenient location on the burner, furnace or wall. The location must not exceed the ambient

temperature limit, 140°F.
Wiring

• Wiring must comply with local and national electrical codes, and with the wiring diagram.

Power input

(red/white wire)

120 VAC, 60 HZ, 9VA

Limit circuit input

(black wire)

)

120 VAC, 60 HZ

Motor load

(orange wire)

10 FLA/ 60 LRA

(reduce by valve load)

Ignitor load

(blue wire)

)

120 VAC, 60 HZ, 500 VA

Vent Input

120 VAC, 60 HZ

Valve load

2 amps

Vent load

0.1 amp

Line Heater

1 amp

Alarm contacts

(dry contacts)

24V, AC/DC, 2A

Operating temperature limits

+32°F to +140°F

Storage temperature limits

-40°F to +185°F

Thermostat anticipator current 0.1 A, AC

Agencies

UL Recognized (US & Canada)

Replaces Carlin, Beckett, Honeywell and ICM

Primary Controls

On-Board LCD Screen

no special tool needed

Valve delay on (0, 3, 10, 15, 30, 60, 120)

Trial for ignition time (15, 30, 45)

Motor Delay Off (0, 10, 15, 30, 120, 300, 900)

Interrupted duty or Smart Ignition operation

Early Spark Termination Timing (0, -5, -10)

• Smart Ignition

Number of recycles (0, 3, Unlimited)

Serviceman reset protection (3)

TT Option (jumpered or open)

Blocked vent protection

Dry set of Alarm contacts

Built-in Pump Prime

Provides cad cell reading in OHMS

Fault history records last 50 fault cycles,

easy to understand icons displayed on screen

for common failures, Valve, Motor, Ignitor

Programmable, Microprocessor Based, Universal Replacement for CAD Cell Oil Burner

Primary Controls