Carlin EZ-Temp 90200HM User Manual

Instructions, Ohm proportional output, Microprocessor-operated

Advertising
background image

135-ohm proportional output

(For regulating 135-ohm modulating devices)

Microprocessor-operated

(Processor coordinates operation and diagnostic)

Easy remote sense

(Electronic sensor, wired to control)

Self-checking program

(Control locks out on diagnostic failure)

Diagnostic/status LED’s

(LED’s indicate power, call for heat, and lockout)

T

ech

support

800-989-2275

carlincombustion.com

Features

• 1 Electronic sensor input
• 1

operating temperature adjustment

• 1 fixed

temperature differential

• 1

modulating band adjustment

• Lockout on diagnostic failure
• Latch-up on hardware failure
• Isolated proportional 135-ohm modulating control output:

90200H — on 3 wires in J-box
90200HT — on 3 terminals on front of control.

Specifications

• Carlin’s Model 90200H microprocessor operated temperature control

is designed to operate 135-ohm modulated devices, replicating older

slidewire devices, and is available in configurations described below.

Note that 90200H/HT controls require a 120-volt power input. The 135-

ohm circuit is isolated.

• For electronic mod motor control systems, such as Siemens SQ5, consult

manufacturer.

• Refer to separate product listing sheets for pre-defined models, or re-

quest a control to meet your specifications (within the available ranges

listed below).

Model

90200H

90200HT

Input power (L1-L2)

120 VAC, 2 VA

Modulating output

Control

Max drive

Balance circuit

3.5 +/- 0.5 VDC, 4.2 +/- 0.2 mA

20 VDC O.C., 6 mA S. C.

Adjustment on rear of control

Connections:

5 wires

(no terminals)

2 wires (120 VAC)

3 terminals (mod)

120 VAC H/N

Red/White & White wires

To “W” on device

To “R” on device

To “B” on device

Yellow/White wire

Yellow/Red wire

Yellow/Black wire

“White” terminal

“Red” terminal

“Black” terminal

Operating temp.

range

Adjustable

(any range between 40°F and 250°F)

Temp. differential

range

Fixed (any value between 1°F and 10°F)

Modulating band

range

Adjustable

(Any range between 10°F and 100°F)

Ambient temp.

limits

+32°F to +140°F (0°C to +60°C)

Storage temp.

limits

-40°F to +185°F (-40°C to +85°C)

Agencies

UL & ULC

Recognized & Listed

Component US and Canada

Instructions

90200H shown — 90200HT also available (with

terminal strip on front for low-voltage connections)

Advertising