Carlin EZ-Temp 90524A User Manual

Instructions, Easy-wire terminal strip microprocessor-operated, Easy remote sense

Advertising
background image

T

ech

support

800-989-2275

carlincombustion.com

Functions

Carlin’s 90524A can be operated as either a triple limit control or a cold-start

control, determined by the setting of the LOW LIMIT adjustment.

Triple limit operation (LOW LIMIT on): Provides adjustable high limit set-

ting and maintains an adjustable minimum temperature in the boiler (low

limit setting) while in stand-by (no space heating call); used for tankless

heater applications. (See Figure 3 , page 4.)
Cold-start operation (LOW LIMIT off): Provides adjustable high limit set-

ting and low temperature protection (delays circulator start until the boiler

is heated above the fixed minimum temperature setpoint); used to prevent

condensation in the boiler on cold start. (See Figure 4 , page 4.)

The 90524A provides input from zone controllers or relays (ZR contact) and

output to enable circulators (C1 contact) or zone controllers (ZC contact).

The gas valve/burner output is on the B1 terminal. Call for heat input is on

the T-T terminals.

Specifications

Carlin’s Model 90524A microprocessor-operated temperature controls are

described below.
Refer to separate product listing sheets for pre-defined models, or request

a control to meet your specifications, within the available ranges listed

below.

Model

90524A

Input power (L1-L2)

120 VAC, 10 VA, 60 Hz

Control power (T-T)

24 VAC, 130 mA

High limit range

Adjustable

High limit differential

Adjustable (fixed if low limit is used or if

differential setpoint is OFF)

Low limit range

Adjustable with OFF position

Low limit differential

Adjustable (fixed if differential setpoint is

OFF)

Low temp function

Low temp differential

Fixed

Fixed

Temperature ranges

Setting —

Differential —

Any value/range between 50° & 250°

Any value/range between 5°F and 100°F

Contact ratings

Full load

Locked rotor

Burner, circulator and ZC contacts

120 VAC, 10 amps (total current on all

contacts not to exceed 16 amps)

120 VAC, 60 amps (total current on all

contacts not to exceed 96 amps)

Ambient temperature

+32°F to +140°F (0°C to +60°C)

Storage temperature

-40°F to +185°F (-40°C to +85°C)

Agencies

UL Listed US and Canada

Instructions

Front

Rear

(size reduced)

Easy-wire terminal strip
Microprocessor-operated

(Processor coordinates operation and diagnostic)

Easy remote sense

(Electronic sensor, wired to control)

Self-checking program

(Control locks out on diagnostic failure)

Diagnostic/status LED’s

(LED’s indicate power, call for heat, and lockout)

SMC technology on burner relay

(lockout when welded contact sensed)