Controller Sensors 750 Series User Manual

Model, Ransducer installation

Advertising
background image

MODEL

750

T

RANSDUCER

INSTALLATION

The Model 750 Pressure Transducer is a

competitively priced, extremely accurate,

auto-zeroing, transducer. The auto-zero

feature occurs approximately every 45

seconds and takes 400 milliseconds to

complete. The patented auto-zeroing

circuit has two main advantages, it

eliminates the need to adjust the zero

point after initial installation, and reduces

long term drift. Pressure ranges available

are 0-0.1” to 0-5” W.C., in four outputs 4-

20mA, 1-5VDC, 1-6VDC and 1-10VDC.

I

NSTALLATION

1. Location- The model 750 pressure

transducer should be placed in as clean,

dry and vibration free a location as

possible.

2. Pressure Connections- The model

750 pressure transducer uses 2 brass

barbed fittings for use with 1/8”or 1/4”

ID vinyl or rubber tubing. Attach tubing

from positive pressure or higher pressure

source to port marked

High (P1) and

lower or negative pressure to

Low (P2)

port. Arrange tubing to minimize stress on

connections. If possible mount with ports

facing down, to aid in moisture drainage.

3. Mounting- Attach the Model 750

Transducer to the mounting surface using

2 fasteners inserted through the two

mounting holes located on the front edge

of the transducer case.

Do not

overtighten. The offset of the 750 series

transducer is set at the factory, but may

need to be adjusted after installation.

NOTE: Allow 5 minutes to warm up

before adjusting the offset.

E

LECTRICAL

C

ONNECTIONS

All electrical connections to the 750 series

transducers are made to the 3 wire pigtail.

The 3 wire pigtail is coded as follows. Red

=

+ Supply, Black = - Supply, Green =

Signal Out. An external power supply

delivering 24 VDC/24 VAC with min

70mA no load, and 100mA peak is

required to drive the unit.

CAUTION:

Do not exceed specified

supply voltage.

Do not apply voltage

to

GREEN wire as permanent

damage will occur.

3

W

IRE

C

ONNECTION

• + Power Supply

• - Power Supply

Signal IN

CONTROLLER

IN +

•red

IN -

•blk

OUT

•grn

3

WIRE TO

2

WIRE CONNECTION

IN +

•red

IN -

•blk

OUT

•grn

• + Power Supply
• - Power Supply

• Signal
• Ctrl Ground

CONTROLLER

4 to 20 mA Output

C

ONVERTING

4-20

M

A

TO

1-5VDC

750 Series Pressure transducers with a 4-

20mA output can be easily adapted to

receivers requiring 1-5 VDC input. Insert

a 250 ohm resistor between the + and –

controller signal input terminals. This will

safely convert the 4 to 20 mA signal to the

desired voltage.

O

FFSET

Remove plug located on the front of the

transducer. With the transducer installed

and no pressure applied, place a meter

between the supply negative and the

output. Turn offset pot to desired reading.

C

USTOMER

S

ERVICE

If any problems are encountered during

installation please call the number below

for assistance.