Controller Sensors 880 Series User Manual

Model, Transducer installation

Advertising
background image

MODEL

880

TRANSDUCER

INSTALLATION

The Model 880 Pressure Transducer is a 2-wire,

4-20mA, compact instrument for measuring

and controlling the many different media that

are compatible with our sensing element.

Positive, negative, and differential pressures can

be measured in ranges from 0-1” WC to 0-15

PSI with a 4-20mA output. Split ranges are also

available.

I

NSTALLATION

1. Location- The model 880 pressure

transducer should be placed in as clean, dry and

vibration free a location as possible.
2. Pressure Connections- The 880 pressure

transducer uses 2 barbed fittings for use with

1/8” ID vinyl or rubber tubing. Attach tubing

from positive pressure or higher pressure

source to port marked

High (P1) and lower or

negative pressure to opposite port

(P2).

Arrange tubing to minimize stress on

connections. If possible, mount with ports

facing down to aid in moisture drainage.
Note: When removing tubing care should be

used to avoid breaking the ports. In some cases

the tubing should be cut off, rather than pulled

off, especially if stiff tubing is being used.
3. Mounting- Attach the Model 880

Transducer to the mounting surface using 2

fasteners inserted through the two mounting

holes located on either the side mounting

flanges, or the holes at the top of the case.

Do

not over-tighten.

E

LECTRICAL

C

ONNECTIONS

All electrical connections to the 880 series

transducer are made to the pluggable screw

terminal block. The block is coded as follows.
1)”+” = Supply Positive,
2) “-“ = Supply (or Controller) Negative.
An external power supply (Vs) delivering 14

- 36 VDC with a minimum of 30mA output

is required to drive the unit. The load must

meet the following requirements:

Minimum Loop Resistance (RLmin):

If Vs<30Vdc, RLmin= 0 ohms

If Vs>30Vdc, RLmin=(Vs-30) x 40 ohms

Maximum Loop Resistance (RLmax):

RLmax=(Vs-14) x 50 ohms

(Example: If Vs=24Vdc, RLmax=500 ohms)

Alternatively, if RL is known:

Vs,min = RL/(50) + 14Vdc

Vs,max = RL/(40) + 30Vdc

CAUTION:

Do not exceed specified

supply voltage.

T

YPICAL

2

WIRE CONNECTION

+

-

• + Power Supply
• - Power Supply

• - Ctrl Negative
• Ctrl Ground

CONTROLLER

4 to 20 mA Output

C

ONVERTING

4-20

M

A

TO

1-5

VDC

880 Series Pressure transducers with a 4-20mA

current output can be easily adapted to

controllers requiring 1-5 VDC input. Insert a

250 ohm resistor between the “+” and “-”

controller input terminals. This will safely

convert the 4-20mA signal to 1-5VDC.

O

FFSET

The offset of the 880 series transducer is

factory set. If it should need adjustment upon

arrival, the offset pot is located next to the ports

on the end of the unit. With the transducer

installed and no pressure applied place a meter

in series with the negative “-“ and the ground.

Turn offset adjusting pot to desired reading.

C

USTOMER

S

ERVICE

If any problems are encountered during

installation please call the number below for

assistance.

Call 1-800-735-8998

7638 Washington Ave S

Eden Prairie, MN 55344

+1.800.735.8998 • +1.952.942.8743

FAX +1.952.942.8753

www.controllersensors.com

IN-880 Rev A