Controller Sensors 885 Series User Manual

Model, Transducer installation

Advertising
background image

MODEL

885

TRANSDUCER

INSTALLATION

The Model 885 Pressure Transducer is a 2-wire,

4-20mA, compact instrument with an LCD

Display. It is used for measuring and controlling

the many different media that are compatible

with our sensing element. Positive, negative, and

differential pressures can be measured in ranges

from 0-1” WC to 0-15 PSI with a 4-20mA

output. Split ranges are also available.

I

NSTALLATION

1. Location- The model 885 pressure transducer

should be placed in as clean, dry and vibration

free a location as possible.
2. Pressure Connections- The 885 pressure

transducer uses 2 barbed fittings for use with

1/8” ID vinyl or rubber tubing. Attach tubing

from positive pressure or higher pressure source

to port marked

High (P1) and lower or negative

pressure to opposite port

(P2). Arrange tubing to

minimize stress on connections. If possible,

mount with ports facing down to aid in moisture

drainage.
Note: When removing tubing care should be

used to avoid breaking the ports. In some cases

the tubing should be cut off, rather than pulled

off, especially if stiff tubing is being used.
3. Mounting- Attach the Model 885 Transducer

to the mounting surface using 2 fasteners inserted

through the two mounting holes located on either

the side mounting flanges, or the holes at the top

of the case.

Do not over-tighten.

E

LECTRICAL

C

ONNECTIONS

All electrical connections to the 885 series

transducer are made to the pluggable screw

terminal block. The block is coded as follows.
1)”+” = Supply Positive,
2) “ - “ = Supply (or Controller) Negative.
An external power supply (Vs) delivering

14 - 36 VDC with a minimum of 30mA output

is required to drive the unit. The load must meet

the following requirements:

Minimum Loop Resistance (RLmin):

If Vs<30Vdc, RLmin= 0 ohms

If Vs>30Vdc, RLmin=(Vs-30) x 40 ohms

Maximum Loop Resistance (RLmax):

RLmax=(Vs-14) x 50 ohms

(Example: If Vs=24Vdc, RLmax=500 ohms)

Alternatively, if RL is known:

Vs,min = RL/(50) + 14Vdc

Vs,max = RL/(40) + 30Vdc

CAUTION:

Do not exceed

specified supply voltage.

T

YPICAL

2

WIRE CONNECTION

885D

+ •

- •

• + Power Supply
• - Power Supply

• - Ctrl Negative
• Ctrl Ground
CONTROLLER

4 to 20 mA Output



C

ONVERTING

4-20

M

A

TO

1-5

VDC

885 Series Pressure transducers with a 4-20mA

current output can be easily adapted to

controllers requiring 1-5 VDC input. Insert a 250

ohm resistor between the “+” and “-” controller

input terminals. This will safely convert the 4-

20mA signal to 1-5VDC.

O

FFSET

The offset of the 885 series transducer is factory

set. If it should need adjustment upon arrival, the

offset pot is located next to the ports on the end

of the unit. With the transducer installed and no

pressure applied place a meter in series with the

negative “-“ and the ground. Turn offset

adjusting pot to desired reading.

C

USTOMER

S

ERVICE

If any problems are encountered during

installation please call the number below for

assistance.

Call 1-800-735-8998